Loading...
HomeMy WebLinkAbout38.121 ORDINANCE NO. 38. 121 AN ORDINANCE OF THE CITY OF SARATOGA AMENDING SECTIONS 3-8, 3-8.2, AND 3-8 OF AETICLE H OF CHAPTER 3 OF THE SARATOGA CITY CODE PERTAINING TO THE ADOPTION BY EEFEEENCE OF THE UNIFORM BUILDING CODE AND AMENDMENTS THEEETO The City Council of the City of Saratoga does hereby ordain as follows: SECTION 1: Section 3-8 of Article II of Chapter 3 of the Saratoga City Code is hereby amended to read as follows: See. 3-8. Uniform Building Code -- Adopted. The 1982 Edition of the Uniform Building Code including Appendix Chapters 1, 7, ll, 12, 23, 32, 35, 38, 49, 51, "' 53, 55 and 57 only, as compiled and published by the International Conference of Building Officials, three copies of which Uniform Building Code have been filed for use and examination by the public in the office of the City Clerk of this city, is hereby referred to and, except as to additions, deletions and amendments hereinafter noted, the same is hereby adopted and made a part hereof, the same as if fully set forth in this Article, and shall be the Building Code for this city. SECTION 2: Section 3-8.2 of Article II of Chapter 3 of the Saratoga City Code is hereby amended to read as follows: See. 3-8.2 Same--Plans and Specificationsi Inspection7 Approval and Maintenance of Facilities. The plans and specifications required by section 302(b) of the Building Code shall include a drainage plan depicting thereon both existing and proposed grades, and all proposed drainage facilities, unless such requirement is waived by the building official. All grading and drainage facilities shall be completed and installed prior to final inspection, and the building official may require certification from the owner, the contractor or a qualified engineer, that all finished grades are in compliance with the approved plans. Neither approval of such drainage plans nor approval of the completed facilities on final inspection shall constitute any representation as to the adequacy of soil or slope stability, nor the adequacy of surface or sub-surface drainage controls, nor that any soil or water- related damage will not occur to the site or to any adjoining property. Maintenance of all on-site drainage facilities, whether or not ultimately connected to a public storm drain, shall be the sole responsibility of the property owner and not the City. -1- SECTION 3: Section 3-9 of Article II of Chapter 3 of the Saratoga City Code is hereby amended to read as follows: Sec. 3-9. Uniform Building Code -- Additions~ Deletions and Amendments. The following additions, deletions and amendments are hereby made to the 1982 Uniform Building Code hereinabove adopted by reference: See. 3-9.1 Reserved. Sec. 3-9.2. Reserved. See. 3-9.3. Reserved. Sec. 3-9.4. Reserved. Sec. 3-9.5. Reserved, Sec. 3-9.6. Reserved. Sec. 3-9.7. Reserved. Sec. 3-9.8. Section 1210 Amended. Section 1210 of the Uniform Building Code, 1982 Edition, is hereby amended to read as follows: Section 1210(a)(1). Findings. Reference is hereby made to Sheets 96, 111, 125 and 126 of the Santa Clara County . Cadastral Planimetries Maps, showing and delineating thereon an area of the City which has been designated as a hazardous fire area, three copies of which Maps have been filed with the Clerk of the City for use and examination by the public, and which Maps are hereby specifically referred to and incorporated herein by reference. Section 9.110 of the Fire Prevention Code of the City of Saratoga defines, inter alia, a "hazardous fire area" as "any land which is covered with grass, grain, brush or forest, whether privately or publicly owned, which is so situated, or is of such inaccessible location, that a fire originating upon such land would present an abnormally difficult job of suppression or would result in great and unusual damage through fire or resulting erosion...." The City Council of the City of Saratoga has found and determined that the area designated as a hazardous fire area on each of the foregoing sheets of the aforementioned Maps does constitute a "hazardous fire area" within the aforementioned definition. The response time of emergency equipment to calls for aid in the hazardous fire area is impaired due to: (1) the non-availability of access to some portions of the hazardous fire area, (2) the existence of steep, narrow streets and roadways located in the hazardous fir~ ~- (3) the lack of connecting streets or road~,'- hazardous fire area, and (4) the unusual topography of the hazardous fire area. Further, the presence of heavy vegetation in the hazardous fire area increases the potential for the rapid spread of any fire which may start in that area, particularly during seasonal dry spells. In order to provide timely life safety warning to inhabitants of residential structures located in the designated hazardous fire area, and to provide the earliest possible opportunity to alert fire suppression personnel of any potential fire condition in the hazardous fire area, it is necessary for the City to amend Section 1210 of the Uniform Building Code, 1982 Edition, per,taining to fire warning and sprinkler systems. (2) Fire Warning Systems. Every dwelling unit and every guest room in a hotel or lodging house used for sleeping purposes shall be provided with smoke detectors conforming to U.B.C. Standard No. 43-6. In dwelling units, detectors shall be mounted on the ceiling or wall at a point centrally located in the corridor or area giving access to rooms used for sleeping purposes. In an efficiency dwelling unit, hotel sleeping room and in hotel suites, the detector shall be centrally located on the ceiling of the main room or hotel sleeping room. Where sleeping rooms are on an upper level, the detector shall be placed at the center of the ceiling directly above the stairway. All detectors shall be located in accordance with approved manufacturer's instructions. When actuated, the detector shall provide an alarm in the dwelling unit or guest room. When alterations, repairs or additions requiring a permit and having a valuation in excess of One Thousand Dollars ($1,000) occur, or when one or more sleeping rooms are added or created in existing Group R, Division 3 Occupancies, the entire building shall be provided with smoke detectors located as required for new Group R, Division 3 Occupancies. In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Smoke detectors may be battery operated when installed in existing buildings, or in buildings without commercial power, or in buildings which undergo alterations, repairs or additions regulated by the second paragraph of this subsection. A smoke detector shall be installed in the basement of dwelling units having a stairway which opens from the basement into the dwelling. Such detector shall be connected to a sounding device or other detector to provide an alarm which will be audible in the sleeping area. -3- (3) Early Warning Fire Reporting System. In addition to the requirements contained in subsection (2) above, an Early Warning Fire Reporting System shall be installed and maintained in a fully operational condition in each new dwelling upon which construction is commenced from and after the effective date of this ordinance in the hazardous fire area described, defined and delineated in subsection (1) above. Further, when an existing dwelling located in the described, defined and delineated hazardous fire area is altered, repaired, added to, or expanded so as to increase the floor space under roof by fifty. percent (50%) or more of the amount of floor space under roof, immediately prior to such alteration, repair, addition or expansion, an Early Warning Fire Reporting System shall be installed and maintained in a fully operational condition in each such dwelling. For the purposes of this paragraph, any alteration, repair, addition or expansion shall be considered as equalling or exceeding the above fifty percent (50%) limit where the work of construction or improvement is done at different time intervals requiring two (2) or more building permits within a period of five (5) years after completion of the first improvement, where although each is for a project emcompassing an addition of less than fifty percent (50%) of increased floor space, but which when combined with other expansions during said five (5) year period of time, increased the amount of floor space under roof by fifty percent (50%) or more of that amount which existed immediately prior to the commencement of the first of the several alterations, repairs, additions, or expansions. An Early Warning Fire Reporting System may be installed in any dwelling located within the city limits of the City of Saratoga other than within that hazardous fire area described, defined and delineated in subsection (1) above. Each Early Warning Fire Reporting System required or permitted to be installed pursuant to this section shall include, contain, and incorporate the following components connected in such a manner as to be capable of automatically transmitting by standard telephone lines or such other means as may be designated and required from time to time by the Board of Fire Commissioners of the Saratoga Fire District, designated alarm signals from any such installation to the Saratoga Fire District Digital Alarm Communicator Receiver: (A) A California State Fire Marshal listed and approved solid state electronic Digital Alarm Communicator Transmitter. A Digital Alarm Communicator Transmitter with provision for connection of supervised integrating zone circuits can be used alone, or any Digital Alarm Communicator Transmitter may be used in conjunction with a California State Fire Marshal listed and approved Fire Alarm Control Panel which meets 'the requirements of National Fire Protection -4- Association Document 72A or 74. If a Fire alarm Control Panel is used, the connection between the Fire Alarm Control Panel and the Digital Alarm Communicator Transmitter shalI be through dry relay contacts on the Fire Alarm Control Panel, or other California State Fire Marshal listed configuration for tile Digital Alarm Communicator Transmitter used. In addition, the Digital Alarm Communicator Transmitter and/or Fire Alarm Control Panel used shall incorporate the following features: (i) The Digital Alarm Communicator Transmitter shall be capable of transmitting to the Saratoga Fire District one or more multiple digit numbers, as may be assigned by the Saratoga Fire District, via commercial telephone lines or such other means as may be designated and required, from time to time, by the Board of Commissioners of the Saratoga Fire District, and shall communicate information in such a manner and of such content as to be compatible with such specifications as may be made and published by the Fire Chief of the Saratoga Fire District. (ii) The Digital Alarm Communicator Transmitter shall be capable of transmitting a separate and distinct code for each of the following conditions: Zone 1.* Smoke detection zone in alarm Zone 2: Heat detection zone in alarm Zone 3: Manual station zone in alarm Zone 4: Sprinkler zone in alarm Zone 5: Medical emergency in alarm Zone 6: Digital Alarm Communieator Transmitter low battery indication Zone 7: Digital Alarm Communicator Transmitter and t~ire Alarm Control Panel general trouble indication Zone 8: Digital Alarm Communieator Transmitter test signal transmission once every 24 hours. If the Digital Alarm Communicator Transmitter and/or the Fire Alarm Control Panel incorporate Class "A" initiating zones, they shall be dedicated to fire alarm zones 1 through 4 above. (iii) The Digital Alarm Communicator Transmitter shall be capable of communicating an entire alarm signal -5- transmission within thirty (30) seconds of the time at which the connection of the ca]] is completed. (iv) The Digital Alarm Communicator Transmitter, and Fire Alarm Control Panel if used, shall contain an internal continuously charging battery, capable of powering the system for a period of at least twenty-four (24) hours in the standby mode, and five (5) minutes under alarm conditions. (v) Electrical supervision of the heat detection zone, manual station zone, and the smoke detection zone (and power to the smoke detectors) shall be provided by the Digital Alarm Communicator Transmitter or the Fire Alarm Control Panel. A single open or ground fault condition in one of these zones in the Digital Alarm Communicator Transmitter, or the Fire Alarm Control Panel, shall be indicated by a distinctive, audible trouble signal in the dwelling in which the system is installed. The Digital Alarm Communicator Transmitter shall also be capable of transmitting a trouble signal to the Saratoga Fire District Digital Alarm Communicator Receiver in the event of a single open or ground fault condition in one of the aforementioned zones in the Digital Alarm Communicator Transmitter or the Fire Alarm Control Panel. (vi) The Digital Alarm Communicator Transmitter employed in the dwelling for transmitting signals shall be capable of assuming line seizure priority over any other Digital Alarm Communicator Transmitter employed for other purposes in the same dwelling. The fire alarm Digital Alarm Communicator Transmitter connections to telephone lines shall be made ahead of those employed for burglar alarm or other purposes, and shall electrically disconnect other Digital Alarm Communicator Transmitters while transmitting signals. (vii) All Digital Alarm Communicator Transmitters shall be capable of being programmed to send signals that are compatible with the Saratoga Fire District Digital Alarm Communicator Receiver, and shall comply with the provisions of Chapter 5 of National Fire Protection Association Document 71. (viii) The Digital Alarm Communicator Transmitter and the Fire Alarm Control Panel shall receive their primary power from the external electrical supply provided to the dwelling and shall be powered by a separate circuit that shall have its own circuit breaker switch. (B) California State Fire Marshal and Underwriter's Laboratory, Inc. approved and listed automatic detectors, capable of responding to visible products of combustion, arranged to communicate with the Digital Alarm Communicator Trmlsmitter or the Fire Alarm Control Panel, and installed in the following locations at points approved by 'the Fire Chief of the Saratoga Fi~'e District in accordance with -6- the standards contained in National Fire Protection Association Document 72E-1982: (i) On the ceiling or wall at a point located in the corridors or areas giving access to rooms used for sleeping purposes. (ii) In each bedroom, located on the ceiling or wall of the room. (iii) On the ceiling or wall near the base of any stairway where sleeping rooms are on an upper level. (C) California State Fire Marshal and Underwriter's Laboratory, Inc. approved and listed automatic detectors, of the combination fixed-temperature rate-of-rise type, arranged to communicate with the Digital Alarm Communicator Transmitter or the Fire Alarm Control Panel, and installed in the following locations at points approved by the Fire Chief of the Saratoga Fire District and in accordance with the standards contained in National Fire Protection Association Document 72E-1982: (i) All rooms in the dwelling, including furnace rooms, excepting those areas specified in subparagraph (B) above, and bathrooms. (ii) Attics. (iii) Garages. Exceptions to these standards may be permitted by the Fire Chief of the Saratoga Fire District. (D) California State Fire Marshal and Underwriter's Laboratory, Inc. approved and listed audible warning devices of sufficient number and adequately located, pursuant to National Fire Protection Association Document 74-1984, within the dwelling living and sleeping areas so as to cause a level of audibility of not less than fifteen (15) decibels above ambient noise levels measured four (4) feet above the floor with bedroom doors closed. (b) Sprinkler S.ystems. When required by other provisions of this Code, automatic sprinkler systems and standpipes shall be installed as specified in Chapter 38 of The Uniform Building Code, 1982 Edition. Notwithstanding any other provisions of The Uniform Building Code, 1982 Edition, as amended, an automatic sprinkler system shall be installed in the garage and/or carport portion(s) of any new dwelling constructed in the hazardous fire area designated, described and delineated in subparagraph (a)(1) above when said garage and/or carport has a capacity to -7- accommodate .three (3) or more automobiles. Further, an automatic sprinkler system shall be installed in the garage and/or carport portion(s) of any existing dwelling located in the described, defined and delineated hazardous fire area, when such dwelling is altered, repaired, added to, or expanded so as to increase the floor space under roof by fifty percent (50%) or more of the amount of floor space under roof, immediately prior to such alteration, repair, addition, or expansion when said garage and/or carport has a capacity to accommodate three (3) or more automobiles. For the purposes of this paragraph, any alteration, repair, addition, or expansion shall be considered as equalling or exceeding the above fifty percent (50%) limit where the work of construction or improvement is done at different time intervals requiring two or more building permits within a period of five (5) years after completion of the first improvement, where although each is for a project emcompassing an addition of less than fifty percent (50%) of increased floor space, but which when combined with other expansions during said five (5) year period of time, increased the amount of floor space under roof by fifty percent (50%) or more of that amount which existed immediately prior to the commencement of the first of the several alterations, repairs, additions, or expansions. Moreover, an automatic sprinker system may be installed in lieu of the approved and listed automatic detector, the combined fixed temperature rate of rise and/or fixed temperature only type, as required in subparagraph (a)(3)(C) above, in those portions of the dwelling identified in subparagraph (a)(3)(C) above. The requirements of subparagraph (a)(3)(B) above must still be complied with regardless of the installation of an automatic sprinkler system. Any automatic sprinkler systems installed pursuant this section shall be installed in accordance with the standards contained in National Fire Protection Association Document 13D and shall be equipped with water flow switches that have a built in retard assembly, which will send an alarm signal to the Digital Alarm Communicator Transmitter or the Fire Alarm Control Panel when the sprinkler system is activated. (c) Early Warning Fire Reporting System--Installation Permit Required. An installation permit shall be obtained from the Saratoga Fire District prior to the installation of any Early Warning Fire Reporting System required or permitted to be installed pursuant to this Section. Suitable documentation relative to the proposed installation shall be submitted to the Saratoga Fire District for approval at the time application is made for such a permit. This documentation shall include the following: (A) A complete list of all fire alarm equipment and devices to be installed, including: -8- (i) Manufacturer's make and model numbers; (ii) Quanities of each type; (iii) California State Fire Marshal listing numbers; (iv) Underwriters' Laboratory, Inc., spacing specifications for heat detectors; (v) Evidence of control panel compatibility with connected smoke detectors. (B) Point to point wiring diagram or electrical sequence list for each zone in a form acceptable to the Saratoga Fire District. Details shall include: (i) Wiring sequence of each initiating zone, including wire size and the number of conductors; (ii) Wiring sequence of each audible circuit, including wire size and the number of conductors; (iii) Identification of the types of initiating devices used; (iv) Temperature ratings indicated, when applicable; (v) Locations of Class "B" circuit end of line devices; (vi) Locations of junction boxes, when installed. (C) If requested, copies of California State Fire Marshal listing data sheets, and any other documents deemed pertinent by the Fire Chief of the Saratoga Fire District. All such systems shall be installed by a person holding a valid fire protection engineering license, C-16 classification, issued by the California Department of Consumer Affairs. All such systems shall be installed in a workmanlike manner and in accordance with the specifications and standards approved by the Saratoga Fire District. Upon completion of the installation, the licensed installer shall instruct the homeowner, or his or her designated representative, in the use of the system and shall provide applicable manufacturer's operating manuals. The Saratoga Fire District shall be responsible for reviewing and approving or disapproving that portion of any and all building plans submitted to the City which are subject to this section. The Saratoga Fire District shall also be responsible for conducting the final inspection and approving or disapproving 'any system installed in a dwelling pursuant to this -9- section. The Saratoga Fire District may establish a fee for the plan review and inspection services it renders pursuant to this section. The licensed installer shall provide the Saratoga Fire District with a set of as built plans for the system." Sec. 3-9.9. Reserved. Sec. 3-9.10. Reserved. Sec. 3-9.11. Reserved. Sec. 3-9.12. Reserved. See. 3-9.13. Reserved. Sec. 3-9.14. Reserved. Sec. 3-9.15. Reserved. SECTION 4: If any section, subsection, sentence, clause or phrase of this Ordinance is for any reason held by a Court of competent jurisdiction to be invalid, such decision shall not affect the validity of the remaining portions of this Ordinance. The City Council of the City of Saratoga hereby declares that it would have passed this Ordinance and each section, subsection, sentence, clause and phrase thereof irrespective of the fact that any one or more sections, subsections, sentences, clauses or phrases may be held invalid or unconstitutional. SECTION 5: This Ordinance shall take effect and be in full force and effect thirty (30) days from and after the date of its passage and adoption. The above and foregoing Ordinance was regularly introduced and after the waiting time required by law, was thereafter passed and adopted this hhiz~fl day of OctDber 1984, by the following vote: ., AYES: CouncilnMmt~rs Callon, Clevenger, Hlava, Moyles and Mayor Fanelli NOES: None ABSENT: None ~'F~ ~f~,-w ~' ~ MAYOR ATTEST: copy of Ordinanc8 ,~3', ('z,/ . which has been -10-