HomeMy WebLinkAbout71.82 ORDINANCE NO. 71. 82
AN ORDINANCE OF THE CITY O1~ SARATOGA AMENDING
SECTION 16-60.020 OF THE CITY CODE CONCERNING
THE EARLY WARNING FIRE ALARM SYSTEM
The City Council of the City of Saratoga ordains as follows:
SECTION h Section 16-60.020 in Article 16-60 of the City Code is amended to
read as follows:
"~16-60.020 Required components
Each early warning fire alarm system installed pursuant to this Article shah
include, contain, and incorporate the following components connected in such a
manner as to be capable of automatically transmitting by standard telephone lines
or such other means as may be designated and required from time to time by the
Board of Fire Commissioners of the Saratoga Fire District, designated alarm signals
from any such installation to the Saratoga Fire District digital alarm communicator
receiver:
(a) Digital alarm eommunieator transmitter. A California State Fire
Marshal listed and approyed solid state electronic digital alarm communicator
transmitter and control panel (either combined with the transmitter or separately
connected thereto) shah be installed with provision for connection of supervised
integrating zone circuits. Such transmitter and control panel shah meet the
requirements of National Fire Protection Association Document 72A or 74 in the
case of residential structures, or Chapter 5 of NFPA Document 71 in the case of
commercial structures, or equivalent method as approved by the Chief of the
Saratoga Fire District. If a separate fire alarm control panel is used, the connection
between the fire alarm control panel and the digital alarm communicator
transmitter shah be through dry relay contacts on the fire alarm control panel, or
other California State Fire Marshal listed configuration for the digital alarm
communicator transmitter can be used. In addition, the digital alarm communicator
transmitter and/or fire alarm control panel used shall incorporate the following
features:
(1) The digital alarm communicator transmitter shah be capable of
transmitting to the Saratoga Fire District one or more multiple
numbers, as may be assigned by the Saratoga Fire District, via
commercial telephone lines or such other means as may be
designated and required, from time to time, by the Board of
Commissioners of the Saratoga Fire District, and shall
communicate information in such a manner and of such content as
to be compatible with such specifications as may be made and
published by the Chief of the Saratoga Fire District.
(2) The digital alarm communicator transmitter shah have a capacity
of not less than eight separate zones and shah be capable of
transmitting a separate and distinct code for each of the following
conditions:
-1-
Zone 1.. Smoke detection zone in alarm
Zone 2: Heat detection zone in alarm
Zone 3: Manual station zone in alarm
Zone 4: Sprinkler zone in alarm
Zone 5: Medical emergency in alarm
Zones 6, 7, 8 As determined by the Saratoga
Fire District
The functions designated for Zones 6, 7 and 8 above may be placed
in that configuration or in an alternative configuration or format
compatible with the Saratoga Fire District digital alarm
communicator receiver. If the digital alarm communicator
transmitter and/or the fire alarm control panel incorporate Class
"A" initiating zones, they shah be dedicated to fire alarm zones 1
through 4 above.
(3) The digital alarm eommunicator transmitter shall be capable of
communicating an entire alarm signal transmission within thirty
seconds of the time at which the connection of the call is
completed.
(4) The digital alarm communicator transmitter, and fire alarm
control panel if used, shall contain an internal continuously
charging battery, capable of powering the system for a period of at
least twenty-four hours in the standby mode, and five minutes
under alarm conditions.
(5) Electrical supervision of the heat detection zone, manual station
zone, and the smoke detection zone (and power to the smoke
detectors) shall be provided by the digital alarm communicator
transmitter or the fire alarm control panel. A single open or
ground fault condition in one of these zones in the digital alarm
eommunicator transmitter, or the fire alarm control panel, shall be
indicated by a distinctive, audible trouble signal in the structure in
which the system is installed. The digital alarm communicator
transmitter shah also be capable of transmitting a trouble signal to
the Saratoga Fire District digital alarm communicator receiver in
the event of a single open or ground fault condition in one of the
aforementioned zones in the digital alarm eommunicator
transmitter or the fire alarm control panel.
(6) The digital alarm communicator transmitter employed in the
structure for transmitting signals shall be capable of assuming line
seizure priority over any other digital alarm communicator
transmitter employed for other purposes in the same structure.
The fire alarm communicator transmitter connections to telephone
lines shah be made ahead of those employed for burglar alarm or
other purposes, and shall electrically disconnect other digital alarm
communicator transmitters while transmitting signals.
-2-
(7) All digital alarm communicator transmitters shall be capable of
being programmed to send signals, over telephone lines and over
radio frequency transmitter, that are compatible with the Saratoga
Fire District digital alarm communicator receiver, which shall be
deemed a remote receiving station as referenced in National Fire
Protection Association Document 72C.
(8) The digital alarm communicator transmitter and the fire alarm
control panel shall receive their primary power from the external
electrical supply provided to the structure and shall be powered by
a separate circuit that shall have its own circuit breaker switch.
(b) Smoke detectors. California State Fire Marshal and Underwriter's
Laboratory, Inc. approved and listed automatic detectors, capable of responding to
visible products of combustion, arranged to communicate with the digital alarm
communicator transmitter or the fire alarm control panel, shall be installed in
accordance with the standards contained in National Fire Protection Association
Document 72E-1982, or as otherwise directed by the Fire Chief. Where any portion
of the structure is used for sleeping purposes, such detectors shall be installed in the
following areas at points approved by the Fire Chief:
(1) On the ceiling or wall at a point located in the corridors or areas
giving access to rooms used for sleeping purposes.
(2) In each bedroom, located on the ceiling or wall of the room.
(3) On the ceiling or wall near the base of any stairway where sleeping
rooms are on an upper level.
(c) Ileat detectors. California State Fire Marshal and Underwriter's
Laboratory, Inc. approved and listed automatic detectors, of the combination fixed-
temperature rate-of-rise type, arranged to communicate with the digital alarm
communicator transmitter or the fire alarm control panel, shall be installed in
accordance with the standards contained in National Fire Protection Association
Document 72E-1982, or as otherwise directed by the Fire Chief. Where any portion
of the structure is used for sleeping purposes, such detectors shall be installed in the
following areas at points approved by the Fire Chief:
(1) All rooms in the dwelling, including furnace rooms, excepting those
areas specified in Paragraph (b) of this Section, and bathrooms.
(2) Attics.
(3) Garages.
Exceptions to these standards may be permitted by the Fire Chief.
(d) Actuating devices. Manual pull stations shall be installed on each floor
of the premises in a visible accessible position, and shall be located in exit ways
adjacent exit doors and doors leading to exit stairs, as determined by the Fire Chief.
Each device shall be securely mounted with the bottom of the device not less than
four and one-half feet nor more than six feet above the floor level.
-3-
(e) Medical emergency push buttons. Medical emergency push buttons shall
be installed in the kitchen area near the telephone and either in or near the master
bedroom. Additional buttons may be required~ as determined by the Fire Chief...
(f) Warning devices. In the case of any structures used for sleeping
purpose"~, California State Fire Marshal and Underwriter's Laboratory, Inc. approved
and listed audible warning devices of sufficient number and adequately located,
pursuant to National Fire Protection Association Document 74-1984, shall be
installed within the sleeping area of the structure so as to cause a level of audibility
of not less than fifteen decibels above ambient noise levels measured four feet
above the floor with bedroom doors closed.
~ Alternative requirements where sprinkler system installed. Where an
automatic sprinkler system is installed equipped with water flow switches that have
a built-in retard assembly which will send an alarm signal when activated to the
digital alarm communieator transmitter or the fire alarm control panel, no heat
detectors as described in Paragraph (c) of this Section shall be required and smoke
detectors as described in Paragraph (b) of this Section shall be required only in those
areas specified in Subparagraphs (b)(1) and (b)(2) of this Section."
SECTION 2: If any section, subsection, sentence, clause or phrase of this
Ordinance is for any reason held by a court of competent jurisdiction to be invalid or
unconstitutional, such decision shall not affect the validity of the remaining portions
of this Ordinance. The City Council of the City of Saratoga hereby declares that it
would have passed this Ordinance and each section, subsection, sentence, clause and
phrase thereof, irrespective of the fact that one or more sections, subsections,
sentences, clauses or phrases may be held invalid or unconstitutional.
SECTION 3: This Ordinance shall be in full force and effect thirty days after its
passage and adoption.
The above and foregoing Ordinance was regularly introduced and after the
waiting time required by law, was thereafter passed and adopted at a regular adjourned
meeting of the City Council of the City of Saratoga held on the 7th day of
Au.qust , 1990, by the following vote:
AYES: Councilmembers Anderson, Clevenger, Kohler, Monia, and Mayor Stutzman
NOES: None
ABSENT: None
' MAY(~R
ATTEST:
~ ~ ~ ~'he above '~nd 'foFcq~iff~ 'is ~ 'true ~hd ~offect
CITY CLERK ,copy ~f Cr.:;n.~n,.c ~_1,_~'~_~__- which has been
'pubfishcd ~ccording to law.
e