Loading...
HomeMy WebLinkAbout02-08-2022 Heritage Preservation Commission Agenda PacketPage 1 of 3 HERITAGE PRESERVATION COMMISSION REGULAR MEETING February 8, 2022 8:30 AM REGULAR MEETING Teleconference/Public Participation Information to Mitigate the Spread of COVID‐19 This meeting will be held entirely by teleconference. All members of the City Council and staff will only participate via the Zoom platform using the process described below. The meeting is being conducted pursuant to recent amendments to the teleconference rules required by the Ralph M. Brown Act allowing teleconferencing during a proclaimed state of emergency when local official have recommended social distancing. The purpose of the amendments is to provide the safest environment for the public, elected officials, and staff while allowing for continued operation of the government and public participation during the COVID-19 pandemic. Members of the public can view and participate in Meeting by: 1. Using the Zoom website https://us02web.zoom.us/j/84035279809 or App (Webinar ID 840 3527 9809) and using the tool to raise their hand in the Zoom platform when directed by the Chair to speak on an agenda item; OR 2. Calling 1.408.638.0968 or 1.669.900.6833, entering the Webinar ID 840 3527 9809 and pressing *9 to raise their hand to speak on an agenda item when directed by the Chair. The public will not be able to participate in the meeting in person. Methods of viewing the meeting will be listed on the meeting agenda. The public will not be able to participate in the meeting in person. In accordance with the Americans with Disabilities Act and the Governor’s Executive Order, if you need assistance to participate in this meeting due to a disability, please contact the City Clerk at bavrit@saratoga.ca.us or calling 408.868.1216 as soon as possible before the meeting. The City will use its best efforts to provide reasonable accommodations to provide as much accessibility as possible while also maintaining public safety. Page 2 of 3 1. Site Visit(s) a. None 2. Call to Order 3. Roll Call- Sharon Boyce-Bender, Marie Lopresto, Rina Shah, and Priya Shastri 4. Oral Communications Any member of the public may address the Commission about any matter not on the agenda for this meeting for up to three minutes. Commissioners may not comment on the matter but may choose to place the topic on a future agenda. 5. Approval of the January 11, 2022 minutes 01-11-22 Heritage Preservation Commission Agenda draft MEETING minutes 6. New Business a. 20601 Brookwood Lane Brookwood Lane 20601 -MEMO Attachment 1-Report from Urban Programmers dated December 22, 2021 and DPR Attachment 2- Site Development Plans 7. Staff Comments a. Heritage Orchard update Orchard Update 02-02-2022 8. Old Business a. Project status worksheet Project Status Worksheet 02-08-2022 9. Commission Items 10. Adjournment In compliance with the Americans with Disabilities Act, if you are a disabled person and you need a disability-related modification or accommodation to participate in this meeting, please contact the City Clerk’s Office at (408) 868-1216 or bavrit@saratoga.ca.us Requests must be made as early as possible and at least one full business day before the start of the meeting. Page 3 of 3 Any recommendation made by the Heritage Preservation Commission may be appealed to the Planning Commission within ten (10) days of the date of the decision. The appeal shall be taken by filing with the Secretary of the Heritage Preservation Commission a written notice and filing fee within ten (10) days of the date of the decision. In accordance with the Ralph M. Brown Act, copies of the staff report, and other materials provided to the Heritage Preservation Commission by City staff in connection with this agenda are available at the office of the Community Development Department Director at 13777 Fruitvale Avenue, Saratoga, California 95070. Any materials distributed by staff after the posting of the agenda are made available for public review at the office of the Director at the time, they are distributed to the Heritage Preservation Commission. CERTIFICATE OF POSTING OF AGENDA I, Nicole Johnson, Senior Planner, for the City of Saratoga, declare that the foregoing agenda for the meeting of the Heritage Preservation Commission was posted and available for public review on February 3, 2022 at the City of Saratoga, 13777 Fruitvale Avenue, Saratoga, CA 95070 and on the City’s website at www.saratoga.ca.us. Page 1 of 3 HERITAGE PRESERVATION COMMISSION REGULAR MEETING DRAFT MINUTES January 11, 2022 8:30 AM REGULAR MEETING 1. Site Visit(s) a. None 2. Call to Order: Chair Shah called the meeting to order at 8:33 AM 3. Roll Call Present: Marie Lopresto, Rina Shah, Priya Shastri, and Joseph Wherry Absent: Sharon Boyce-Bender Staff: Nicole Johnson, Senior Planner Applicants: John Frolli and Jorge Sanchez 4. Election of 2022 Chair and Vice Chair SHAH/WHERRY MOVED TO NOMINATE MARIE LOPRESTO AS CHAIR. LOPRESTO DECLINED THIS NOMINATION. LOPRESTO/SHAH MOVED TO NOMINATE PRIYA SHASTRI AS CHAIR. MOTION PASSED. AYES: LOPRESTO, SHAH, SHASTRI, WHERRY. NOES: NONE. ABSTAIN: NONE. ABSENT: BOYCE-BENDER SHAH MOVED TO NOMINATE JOSEPH WHERRY AS VICE CHAIR. WHERRY DECLINED THIS NOMINATION. SHASTRI/SHAH MOVED TO NOMINATE MARIE LOPRESTO AS VICE CHAIR. MOTION PASSED. AYES: LOPRESTO, SHAH, SHASTRI, WHERRY. NOES: NONE. ABSTAIN: NONE. ABSENT: BOYCE-BENDER Chair Shastri took over the meeting. 5. Oral Communications 3 Page 2 of 3 Marilyn Marchetti spoke about the proposed windows for the John Henry house and encouraged the HPC to review the original report on the property from 2018. 6. Approval of the December 14, 2021 minutes LOPRESTO/SHAH MOVED TO APPROVE THE MINUTES FOR THE DECEMBER 14, 2021 MEETING. MOTION PASSED. AYES: LOPRESTO, SHAH, SHASTRI, AND WHERRY. NOES: NONE. ABSTAIN: NONE. ABSENT: BOYCE-BENDER 7. New Business a. 14630 Big Basin Way Continued at the request of the applicant to a future date b. 14275 Saratoga Avenue Nicole Johnson provided a reported summary of the memo for the project. John Frolli expanded on the proposal for the residence and answered questions from the commissioners. SHAH/LOPRESTO MOVED TO RECOMMEND APPROVAL FOR THE ADDITION AND REHABILITATION WITH THE CONDITION THAT THE WINDOWS TO BE REPLACED WILL BE WOOD AND THE REPLACEMENT EXTERIOR MATERIALS MATCH THE EXISTING AS CLOSELY AS POSSIBLE. MOTION PASSED. AYES: LOPRESTO, SHAH, SHASTRI, AND WHERRY. NOES: NONE. ABSTAIN: NONE. ABSENT: BOYCE-BENDER. 8. Staff Comments Nicole Johnson and the commissioners welcomed Joseph Wherry to the HPC. 9. Old Business a. Heritage Preservation Ordinance update SHAH/WHERRY MOVED TO RECOMMEND THAT THE CITY COUNCIL ACCEPT THE HPC PROPOSED CHANGES TO THE HP ORDINANCE AS PROVIDED IN ATTACHMENT 2. MOTION PASSED. AYES: LOPRESTO, SHAH, SHASTRI, AND WHERRY. NOES: NONE. ABSTAIN: NONE. ABSENT: BOYCE-BENDER. b. Project status worksheet Commissioners will look at the projects that former Commissioner Stransky and consider working on. 10. Commission Items Lopresto would like to look into establishing a historic district/heritage lane from Madrona Cemetery to Lutheria Ave. 4 Page 3 of 3 11. Adjournment Chair Shastri adjourned the meeting at 9:24 AM. Minutes respectfully submitted: Nicole Johnson, Senior Planner City of Saratoga 5 Page 1 of 2 MEMORANDUM MEETING DATE: February 8, 2022 TO: Heritage Preservation Commission (HPC) FROM: Nicole Johnson, Senior Planner SUBJECT: Item 6a-20601 Brookwood Lane APPLICATION: HPC22-0001 Property Location: 20601 Brookwood Lane Property APN: 503-23-022 Property Owner/Applicant: Ben & Annalisa Tkacheff Background: The subject property is listed on the Heritage Resource Inventory as a heritage resource (HP-88-01) as the Willlard House. This Craftsman-era house sits in a wooded setting that almost entirely screens it from the public right-of-way. The side-gabled house features a shed dormer, unpainted siding, and original wood windows. According to previous records, alterations and additions to the original structure were well integrated into the original design. The house and garage originally had copper roofs; the roof of the house has been replaced but the copper roof of the garage remains. Major alterations and additions include a library and deck off the dining room added in 1965, conversion of a screened porch to an office in 1970, and a "Great Hall" and master bedroom with deck on the second floor added in 1980. Project Description: The applicant is requesting the following exterior modifications: 1. Relocation of the front entry door. Currently the main entry is on the west side of a projecting gable, and not visible from the front view. The relocation to the west side of the front façade is a change to the design. However, reusing the existing door system and sidelights, will not have an adverse change to the overall design. The relocation will require removing 3 hung windows that 6 Page 2 of 2 appear to be original. The wall where the existing door is located will be fitted with a new window that matches (size, style, and materials), the one on the other side of the projecting front gable. 2. Rear Façade: Upper window to be replaced in style with tempered pane (adjacent to wet bathroom surface). This is a code requirement. 3. Rear Façade: Redesign window pattern on the rear wall to provide a second doorway that will share an entry porch with the existing door and window. The new door replaces an existing contemporary window. 4. Standard window removal. Four non-original rear windows will be removed, and one new window installed. The style and materials are compatible with the existing building 5. Remove a non-original French door and replace with tri-parte window. The applicant has provided a memo from Urban Programmers who evaluated the proposed project and found that that the proposed changes to the house do not create a significant change to the building or to the environment. The materials and styles of the exterior changes are compatible with the existing building. Staff Recommendation: Staff recommends that the HPC consider the applicant’s request for the exterior modifications and recommended approval of the project. Attachments: 1. Report from Urban Programmers dated December 22, 2021 and DPR. 2. Plans 7 Susan Walsh, AICP Historic Preservation Officer City of San Jose 200 E. Santa Clara Street San Jose CA Re: 196 N. 3rd Street, San Jose CA Dear Ms. Walsh, he referenced property, also known as the former Scottish Rite Temple or the San Jose Athletic Club is listed in the National Register, and is a historic resource as defied by CEQA. The City of San Jose has asked if the rehabilitation be consistent with the Secretary of the Interior’s Standards for Rehabilitation. Urban programmers was contacted by T. Corona, on behalf the owner to provide a third party professional review of the rehabilitation plans for consistency with the “Standards.” The rehabilitation work that is proposed is to a front open area in front of the historic building and not to the historic building. Background: The Scottish Rite Bodies had this building, their second Temple in San Jose, was designed by Carl Warner who specialized in Masonic architecture in Northern California. The building was constructed in 1924, completed and dedicated in 1925. The Neo-Classic designed building exhibits a continuity of architectural design within the St. James Square Historic District in its columns and ornate detailing – some in Egyptian motifs. The front façade is a symmetrical temple design with a broad stair in the center beginning at the edge of the sidewalk and raising to the first story, and projecting portico with 6 fluted Ionic columns. Both sides of the building recess from the portico and are mirror images of design with evenly spaced windows on the two upper floors and mirror elements on the ground level. Elaborately framed niches are behind tall base structures with Sphinx statues on the top. Further exhibiting the symmetrical design, on each side of the stairs are tall winged Sphinx sculptures with basins on the top representing torches. The building had an auditorium that could seat 1,400 and the largest stage in San Jose, a large kitchen, meeting rooms and a basement that was finished and used as a second or informal hall. By the 1960s the Scottish Rite Bodies were looking for a more convenient location, purchasing acreage and eventually constructing a new Temple in the Willow Glen area, In 1980, the historic building was sold and rehabilitated at a cost of $6,000,000, opening in 1981, as the San Jose Athletic Club. This rehabilitation altered the symmetrical design of the front landscaping by introducing a sectioned ramp on the south side of the property that extends the width of the property on that side accessing the basement from the street. Boxwood, oleander and small bushes were planted against the face of the building and along the ramp. The north side landscaping remained with a patch of lawn and low boxwood hedges in front of the building. During the 1980 rehabilitation, pine trees were planted along the north side of the building. Left untrimmed for many years these began to damage the building and were removed. Nicole Johnson, Senior Planner City of Saratoga Community Development Department 13777 Fruitvale Avenue Saratoga, CA 95070 Dear Nicole, Urban Programmers was asked by Mark DeMattei, DeMattei Construction, to review proposed exterior alterations to the house at 20601 Brookwood Lane in Saratoga. The property is listed in the Saratoga Historical Resources Inventory. The DPR is attached to this letter. Methodology: Review the existing DPR for the property. We studied photographs of the house and the plans prepared by DeMattei Construction, particularly Sheets A3.1 and A5.1 (exterior elevation of existing and proposed). We observe that extensive alterations to the building have occurred over time. The proposed changes occur in areas that have been added or previously altered and are primarily on the rear façade (N), however relocating the front entry door and sidelights is a change to the front (S) and side façade (W). Purpose of the proposed changes: the proposed reorienting of some windows and doors is to align with changes to the interior creating a more usable circulation and comfortable design for interior space. Review context and findings: The 1.5 story building has a cross gable roof structure with gable dormers on each side. The front façade exhibits , 4 gables facing to the front, and a section of shed roof on a projecting element to the left of center, however the building does not have a symmetrical design and appears to have has several remodels since it was constructed in 1919. 1. Relocation f the front entry door. Currently the main entry is on the west side of a projecting gable, and not visible from the front view. The relocation to the west side of the front façade is a change to the design. However, reusing the existing door system and sidelights, will not have an adverse change to the overall design. The relocation will require removing 3 hung windows that appear to be original. The wall where the existing door is located will be fitted with a new window that matches (size, style, and materials), the one on the other side of the projecting front gable. 2. Rear Façade: Upper window to be replaced in style with tempered pane (adjacent to wet bathroom surface). This is a code requirement. 3. Rear Façade: Redesign window pattern on the rear wall to provide a second doorway that will share an entry porch with the existing door and window. The new door replaces an existing contemporary window. 4. Standard window removal. Four non-original rear windows will be removed, and one new window installed. The style and materials are compatible with the existing building 5. Remove a non-original French door and replace with tri-parte window. December 22, 2021 8 Page 2 20601 Brookwood La, Woodside None of the proposed changes to the windows and doors on the rear façade of the house involve original/historic materials. The rear of the building has been extensively altered. The proposed changes are compatible with the design and do not diminish the overall architectural design of the existing house. Relocating the front entry door is a change to the primary façade of the building. In this case the façade has been altered and enlarged since the house was originally constructed in 1919. At this time we were not able to determine the past configuration and are relying upon changes in methods and materials that are visible. In summary, the proposed changes to the house at 20601 Brookwood, do not create a significant change to the building or to the environment. The materials and styles of the exterior changes are compatible with the existing building. No historic fabric is part of the proposed changes. Best regards, Bonnie Bamburg 9 Mount Diablo State of California - The Resources Agency DEPARTMENT OF PARKS AND RECREATION PRIMARY RECORD NRHP Status Code 4of Willard House*Resource Name or # HP-88-01 P1. Other identifier: *P2. Location: Santa Clara County*a. County Cupertino*b. USGS 7.5' Quad 1980 Photorevised .8 S.T .1 W.R Brookwood Lane c. Address:SaratogaCity 95070Zip 10S d. UTM:(give more than one for large and/or linear resources) Zone mE/mN north side of Brookwood Lane west of Saratoga-Sunnyvale Road. e.Other Locational Data: (e.g., parcel #, directions to resource, elevation, etc., as appropriate) (Assigned by recorder): and (P2b and P2c or P2d. Attach a location map as necessary.) ;; ; This large one-and-one-half-story, multi-gabled residence is surrounded by extensive gardens on a spacious lot; it is barely visible from the public right-of-way. The split bargeboards, wide roof, and knee braces are typical of a Craftsman bungalow; houses from the Craftsman era— about 1905 to 1925—embody a local design response to the Arts-and-Crafts movement, as presented in such historic magazines as Craftsman. The walls are clad in horizontal, wood lap siding with possible replacement windows that fit within original trim. The porches on the south and east sides have French doors opening from first floor. A small barn, carriage house and shed on the property are well maintained, as is a gazebo in the rear garden and an arbor in the front garden. Other than the possible changes to the windows, there do not appear to have been any major alterations or additions to the house and it appears in excellent condition. *P3a. Description: (Describe resource and its major elements, include design, material, condition, alterations, size, setting, and boundaries) HP2. Single family property*P3b. Resource Attributes: (List attributes and codes) Building Structure Object Site District Element of District Other (Isolates, etc.)*P4. Resources Present: None Location Map Sketch Map Continuation Sheet Building, Structure, and Object Record Archaeological Record District Record Linear Feature Record Milling Station Record Rock Art Record Artifact Record Photograph Record Other (List): *Attachments: Archives & Architecture: City of Saratoga Statement of Historic Context, 2009. *P11. Report Citation: (Cite survey report and other sources, or enter "none".) View facing north, July 2009. P5b.Description of Photo: (View, date, accession #) Historic Prehistoric Both *P6. Date Constructed/Age and Source: Ian & Helen Whiting 20601 Brookwood Lane Saratoga CA 95070 *P7. Owner and Address: Archives & Architecture, LLC PO Box 1332 San Jose, CA 95109 *P8. Recorded By: (Name, affiliation, and address) 10/26/09*P9. Date Recorded: Reconnaissance *P10. Survey Type: (Describe) 1916, 93 years old. * Required InformationDPR 523A (1/95) Not for Publication Unrestricted 1 503-23-022APN# B.M. F. Maggi, L. Dill, & J. Kusz Date Primary # HRI # Trinomial Other Listings Review Code Reviewer Date Page 20601 10 State of California - The Resources Agency DEPARTMENT OF PARKS AND RECREATION BUILDING, STRUCTURE, AND OBJECT RECORD 3CS*NRHP/CRHR Status Code Willard HouseResource Name (Assigned by recorder) 4of F. B. Willard House B1. Historic Name: 20601 Brookwood Lane B2. Common Name: Single family residential B3. Original Use:Single family residentialB4. Present Use: Craftsman*B5. Architectural Style: Constructed circa 1916. *B6. Construction History: (Construction date, alterations, and date of alterations) No Yes Unknown*B7. Moved?n/aDate:n/aOriginal Location: Small barn, carriage house *B8. Related Features: Unknown B9a. Architect:Unknownb. Builder: Architecture*B10. Significance: Theme Congress Springs / Pierce RoadArea: c1916Period of Significance:ResidentialProperty Type:(3)Applicable Criteria: (Discuss importance in terms of historical or architectural context as defined by theme, period and geographic scope. Also address integrity.) The Willard House is listed on the Saratoga Heritage Resources Inventory, included as a part of HP-88-01. It qualified under Criteria a and c: a) the property exemplifies and reflects special elements of the cultural, social, economic, aesthetic, and architectural history of Saratoga; and c) the property embodies distinctive characteristics of the Craftsman style, type and period. The Willard House also appears eligible for the California Register of Historical Resources under Criterion (3), as the house embodies the distinctive characteristics of the Craftsman house-type within Saratoga's City of Homes period. (Continued on page 4, DPR523L) DPR 523B (1/95)*Required Information B11. Additional Resource Attributes: (list attributes and codes) Saratoga Heritage Preservation Commission, Historic Resources Inventory form, 1988. *B12. References: a,c c,d Listed Heritage Resource B13. Remarks: Franklin Maggi*B14. Evaluator: October 26, 2009*Date of Evaluation: (Sketch Map with north arrow required.) (This space reserved for official comments.) 2 None Primary # HRI # Page 11 State of California - The Resources Agency DEPARTMENT OF PARKS AND RECREATION LOCATION MAP 4of DPR 523J (1/95)*Required Information * Map Name:Multiple n.t.s.* Scale:Varies* Date of Map: Willard House*Resource Name or #(Assigned by recorder)3 Primary # HRI # Trinomial Page 12 State of California - The Resources Agency DEPARTMENT OF PARKS AND RECREATION CONTINUATION SHEET 4of DPR 523L (1/95)*Required Information (Continued from page 2, DPR523b, B10) Historical Background This residence was built in 1916 for F.B. Willard, an executive of the "City of Paris" department store in San Francisco. He lived here until the 1950s. In the 1950's Dr. McKuen, a dentist, purchased the house from the Willards. In 1959, the house was sold to John Kahle who lived here until at least the 1980s. Although the architect is unknown, notes provided by the Kahle family at the time of the 1980s recording indicate an association with Julia Morgan. This information could not be confirmed as a part of this study. Integrity The house and outbuildings retain adequate architectural design, workmanship and materials, as well as a compatible setting and original location, and the property continues to represent the historical associations and feelings of this residence. * Recorded By F. Maggi, L. Dill, & J. Kusz Willard House*Resource Name or #(Assigned by recorder) Continuation Update10/26/2009* Date Primary # HRI # Trinomial Page 4 13 DN DN UP UP UP UP 7 1/4 : 127 1/4 : 127 1/4 : 127 1/4 : 127 1/4 : 12 7 1/4 : 12 1 A3.1 2 A3.1 3 A3.1 4 A3.1 UP UP UP 7 1/4 : 127 1/4 : 127 1/4 : 12BALCONYDECK7 1/4 : 127 1/4 : 12 7 1/4 : 12 FIRST FLR. OUTLINE SECOND FLR. OUTLINE FIRST FLR. OUTLINE SECOND FLR. OUTLINE LIGHT-WELL LIGHT-WELLLIGHT-WELLLIGHT-WELL STAIRS TO BASEMENT ENTRY LANDING (E) ELEC. METER SL.7 1/4 : 127 1/4 : 12SL. SL. SL. SL. SL. SL. SL. SL. N CL X COVER SHEETSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 CSDESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.CITY OF SARATOGA: CONSTRUCTION WORK HOURS: MONDAY - FRIDAY 7:30AM - 6:00PM SATURDAYS 9:00AM - 5:00PM SUNDAYS AND WEEKDAY HOLIDAYS PROHIBITED SITE MANAGEMENT: A.SITE SHALL BE MAINTAINED CLEAN AT ALL TIMES AND CONSTRUCTION DEBRIS HAULED OFF ON A REGULAR BASIS. B."BEST MANAGEMENT PRACTICE" SHALL BE IN PLACE AND MAINTAINED DURING THIS PROJECT FOR PROTECTION OF ANY POLLUTANTS ENTERING THE EXISTING STORMWATER SYSTEM. COVERSHEET NOTES FOR SARATOGA RESPONSES TO PLAN CHECK COMMENTSFill out "Tools>Project Information> Client Information" topopulate client information on cover sheet and title block. PROJECT DATA ZONING R-1-15 OCCUPANCY TYPE R-3/U BUILDING TYPE V-B NON-SPRINKLERED APN 503-23-022 GROSS LOT AREA 63,597 SF FLOOR AREA: (E) 1ST FLR.2,202 SF (E) 2ND FLR.1,365 SF TOTAL FLR. AREA 3,567 SF (E) BASEMENT 1,708 SF REMODELED AREA: 1ST FLR.1,069 SF 2ND FLR. 619 SF TOTAL 1,688 SF SPECIAL INSPECTION CONSTRUCTION SHALL CONFORM TO: 2019 California Building Code 2019 California Residential Code 2019 California Plumbing Code 2019 California Mechanical Code 2019 California Electrical Code 2019 Energy Code 2019 Green Building Code 2019 California Fire Code 2019 California Reference Standards Code COVERSHEET GENERAL NOTES, CALGREEN CHECKLIST AND NOTES SHEET INDEX PROJECT DIRECTORY SCOPE OF WORK: PARTIAL INTERIOR REMODEL OF FIRST FLOOR AND SECOND FLOOR. NO CHANGES TO BASEMENT. NO ADDITION. PROPERTY OWNER: ANNALISA & BEN TKACHEFF 20601 BROOKWOOD LANE SARATOGA, CA 95070 DESIGNER/CONTRACTOR: DE MATTEI CONSTRUCTION 1794 THE ALAMEDA SAN JOSE, CA. 95126 (408) 350-4200 SPECIAL INSPECTION NOTES LOCATION MAP PARCEL MAP N Scale: 1/4"=1'-0" EXISTING ROOF PLAN PROJECT LOCATION ToDo: 1.PLACE HOLDER, BECAUSE IT WON'T FORMAT WITHOUT IT. SHEET INDEX CS COVER SHEET T-1 TITLE 24 ENERGY COMPLIANCE T-2 TITLE 24 ENERGY COMPLIANCE A0.0 GENERAL NOTES A2.1 EXISTING FLOOR PLANS A2.2 EXISTING FLOOR PLANS A2.3 EXISTING FLOOR PLANS A3.1 EXISTING ELEVATIONS A4.1 PROPOSED FLOOR PLANS A4.2 PROPOSED FLOOR PLANS A5.1 PROPOSED EXTERIOR ELEVATIONS A6.1 BUILDING SECTIONS S0.1 GENERAL NOTES S0.2 GENERAL NOTES S1.0 FOUNDATION PLAN S1.1 FIRST FLOOR FRAMING PLAN S1.2 SECOND FLOOR FRAMING PLAN S1.3 ROOF FRAMING PLAN S6.1 TYPICAL WOOD DETAILS S6.2 TYPICAL WOOD DETAILS S7.1 TYPICAL FRAMING DETAILS T KACHEFF RESIDENCE Added 12/10/19 ABBREVIATIONS: A.B.ANCHOR BOLT A.D.AREA DRAIN ADJ.ADJUSTABLE A.F.F.ABOVE FINISHED FLOOR AL.ALUMINUM BD.BOARD BLK.BLOCK BLKG.BLOCKING BM.BEAM CAB.CABINET C.B.CARRIAGE BOLT OR CEILING BEAM OR CATCH BASIN CEM.CEMENT C.J.CEILING JOIST OR CONTROL JOINT CLG.CEILING CLR.CLEAR C.O.CLEANOUT OR CASED OPENING COL.COLUMN CONC.CONCRETE CONSTR.CONSTRUCTION CONT.CONTINUOUS DBL.DOUBLE DED.DEDICATED DEPT.DEPARTMENT DET.DETAIL DIA.DIAMETER DIM.DIMENSION DN.DOWN DR.DOOR DS.DOWNSPOUT E.EAST EA.EACH E.J.EXPANSION JOINT ELEC.ELECTRICAL EQ.EQUAL EQUIP.EQUIPMENT (E)EXISTING EXP.EXPOSED OR EXPANSION EXT.EXTERIOR F.A.FIRE ALARM F.A.U.FORCED AIR UNIT FDN.FOUNDATION F.E.FIRE EXTINGUISHER F.E.C.FIRE EXTINGUISHER CABINET F.F.FINISH FLOOR FIN.FINISH FIXT.FIXTURE FLSH.FLASHING FLR.FLOOR(ING) FLUOR.FLUORESCENT F.O.F.FACE OF FINISH F.O.H.C.FREE OF HEART CENTER F.O.S.FACE OF STUD FTG.FOOTING GA.GAUGE GALV.GALVANIZED GFCI GROUND FAULT CIRCUIT INTERRUPTER GL.GLASS GR.GRADE G.S.M.GALVANIZED SHEET METAL GYP.BD.GYPSUM BOARD HB HOSE BIB HD.HEAD HDWR.HARDWARE HE HIGH EFFICACY I.D.INSIDE DIAMETER (DIM.) INCL.INCLUDE INSUL.INSULATION INT.INTERIOR JAN.JANITOR JST.JOIST JT.JOINT KD.KILN-DRIED LAM.LAMINATE(D) LOCS. LOCATIONS MAX.MAXIMUM MECH.MECHANICAL MEMB.MEMBRANE MIN.MINIMUM MTD.MOUNTED MTL.METAL (N)NEW N.I.C.NOT IN CONTRACT NO.OR#NUMBER N.T.S.NOT TO SCALE O/OVER OA.OVERALL O.C.ON CENTER O.D.OUTSIDE DIAMETER (DIM.) OFCI OWNER FURNISHED, CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED OH OVERHEAD O.L.OUTDOOR LIGHT OPNG.OPENING OPP.OPPOSITE PERF.PERFORATED PL.PLATE OR PROPERTY LINE P.LAM.PLASTIC LAMINATE PLAS.PLASTER PLYWOOD.PLYWOOD PR.PAIR PT.POINT R.RADIUS OR RISER REF.REFERENCE REINF.REINFORCE REQ'D REQUIRED RESIL.RESILIENT R.O.ROUGH OPENING R.O.W.RIGHT OF WAY SCD.SEE CIVIL DRAWINGS SCHED.SCHEDULE S.D.SMOKE DETECTOR SECT.SECTION SEL.SELECT SH.SHELF OR SHELVING SHT.SHEET SIM.SIMILAR SL.SKYLIGHT SLD.SEE LANDSCAPE DRAWINGS SPEC.SPECIFICATION(S) S.Q.SQUARE SSD.SEE STRUCTURAL DRAWINGS SST.STAINLESS STEEL STD.STANDARD STL.STEEL SURF.SURFACE SUSP.SUSPEND SYM.SYMBOL OR SYMMETRICAL T.TREAD TEMP.TEMPERED TOC.TOP OF CURB TOP.TOP OF PAVEMENT TOW.TOP OF WALL T.P.TOP PLATE TYP.TYPICAL UON.UNLESS OTHERWISE NOTED VCT.VINYL COMPOSITION TILE VERT.VERTICAL VIF.VERIFY IN FIELD W/WITH WD.WOOD WH WATER HEATER WP.WATERPROOF AS SHOWN TRUE NORTH CENTER LINE FENCE X XX X XX SECTION. #/SHEET KEY NOTE# DOOR SYMBOL# WINDOW SYMBOL# SYMBOLS: ENERGY CONSULTANT: FRI ENERGY CONSULTANTS, LLC 21 N. HARRISON AVE, SUITE 210 CAMPBELL, CA 95008 (408) 866-1620 STRUCTURAL ENGINEER: DAEDALUS STRUCTURAL ENGINEERING 12930 SARATOGA AVE, B9 SARATOGA, CA 95070 (408) 517-0373 14 UP 2668 2668 806860684068 3036DH 21040DH 21040DH 21040DH 21040DH 306821040DH21040DH21040DH21040DH21040DH21040DH2668 266826682068 28682668 2668 3068 21040DH21040DH UP 1 A3.1 2 A3.1 3 A3.1 4 A3.1 LAUNDRY CLOSET F.C. 7'-0" BATH CRAWLSPACE UTILITY MEDIA MEDIA STORAGE CLOSET CLO.STORAGE WINE (E) FAU LIGHT-WELLLIGHT-WELL LIGHT-WELLLIGHT-WELLLIGHT-WELL EXISTING FLOOR PLANSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A2.1DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.GREEN BUILDING: FINISHES: A.USE LOW-VOC INTERIOR WALL/CEILING PAINTS (<50 GRAMS PER LETTER (GPL) VOCS REGARDLESS OF SHEEN) CGBSC 4.504.2.2 B.USE LOW-VOC COATINGS THAT MEET SCAQMD RULE 1113 (CGBSC 4.504.2.3) PLUMBING: ALL EXISTING NON-COMPLIANT PLUMBING FIXTURES SHALL BE UPGRADED: A.WATER CLOSETS WITH A FLOW RATE IN EXCESS OF 1.6 GPF WILL NEED TO BE REPLACED WITH WATER CLOSETS WITH A MAXIMUM FLOW RATE OF 1.28 GPF. B.SHOWER HEADS WITH A FLOW RATE GREATER THAN 2.5 GPM WILL NEED TO BE REPLACED WITH A MAXIMUM 2.0 GPM SHOWER HEAD. C.LAVATORY AND KITCHEN FAUCETS WITH A FLOW RATE GREATER THAN 2.2 GPM WILL NEED TO BE REPLACED WITH A FAUCET WITH MAXIMUM FLOW RATE OF 1.2 GPM (OR 1.8 GPM FOR KITCHEN FAUCETS). LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED NEW INTERIOR CONSTRUCTION; 2x4 WD. STUD, 1/2" GYP. BD. EACH SIDE NEW EXTERIOR CONSTRUCTION; SEE 5/A3.2 NEW 1-HR FIRE RATED WALL; 2x4 WD. STUD, 5/8" TYPE "X" GYP. BD. EACH SIDE. SEE PLAN FOR LOCATIONS. LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED LEGEND: EXISTING CONSTRUCTION NEW CONSTRUCTION updated 08/15/19Plumbing changes; showerhead flow rates. LAUNDRY/BATHROOM VENTILATION: FOR LAUNDRY ROOMS AND BATHROOMS WITHOUT AN OPERABLE WINDOW: A.PROVIDE MECHANICAL VENTILATION SYSTEM CAPABLE OF 5 AIR CHANGES/HR. TO EXTERIOR. B.USE SMOOTH METAL DUCT FOR DRYER EXHAUST WITH A MAX. LENGTH OF 14', TO OUTSIDE WITH BACKDRAFT DAMPER AND TWO 90° ELBOWS AND A MIN. OF 4" DIA. C.TERMINATION OF ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MINIMUM OF 3 FEET FROM PROPERTY LINES OR ANY OPENINGS INTO THE BUILDING (i.e., DRYERS, BATH AND UTILITY FANS, ETC., MUST BE 3 FEET AWAY FROM DOORS WINDOWS, OPENING SKYLIGHTS OR ATTIC VENTS). D.EXHAUST FANS SHALL HAVE A MIN. OF 50 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR CONTINUOUS VENTILATION AND BE ENERGYSTAR COMPLIANT AND BE EQUIPPED WITH A HUMIDISTAT AND HUMIDITY CONTROL. AND BE SWITCHED SEPARATELY FROM LIGHTING SYSTEM. PLUMBING: A.ALL NEW TOILETS SHALL HAVE AN EFFECTIVE FLUSH VOLUME NOT TO EXCEED 1.28 GALLONS PER FLUSH. B.ALL NEW LAVATORY FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.2 GALLONS PER MINUTE AT 60 PSI. C.ALL NEW SHOWERHEADS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. D.MULTIPLE SHOWERHEADS SERVING ONE SHOWER - COMBINED FLOW RATE OF ALL SHOWERHEADS AND/OR OTHER SHOWER OUTLETS CONTROLLED BY A SINGLE VALVE SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. E.ALL NEW KITCHEN FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN FAUCETS MAY TEMPORARILY INCREASE THE FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER MINUTE AT 60 PSI AND MUST DEFAULT TO A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN ELECTRICAL: A.ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER(AFCI). B.PROVIDE AFCI AND GFCI PROTECTION AT ALL RECEPTACLES SERVING KITCHEN COUNTERTOPS. C.AT EACH KITCHEN AND DINING AREA COUNTER SPACE WIDER THAN 12", LOCATE A RECEPTACLE SO THAT NO POINT ALONG THE COUNTER WALL IS OVER 24" FROM A RECEPTACLE. COUNTERTOP RECEPTACLES REQUIRED WITHIN 24" EACH SIDE OF A BREAK IN THE CONTINUOUS COUNTERTOP SURFACE (SINKS-STOVES). D.REQ'D RECEPTACLES MOUNTED ON THE SIDES OF CABINETS SHALL BE A MAXIMUM OF 12" BELOW THE COUNTERTOP SURFACE WITH A MAXIMUM OF 6" COUNTERTOP OVERHANG. E.PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS FOR COUNTER RECEPTACLES. SMOKE DETECTORS: A.SMOKE DETECTOR SYSTEM SHALL BE HARD WIRED, INTERCONNECTED TO SOUND SIMULTANEOUSLY AND EQUIPPED WITH BATTERY BACKUP. B.INSTALL DETECTORS IN EACH BEDROOM, AT EACH CORRIDOR/AREA NEXT TO THE BEDROOM, AT THE TOP OF STAIRS AND EACH STORY AND BASEMENT. C.MULTIPLE SMOKE DETECTORS ARE REQUIRED WHEN CEILING LEVELS/ ELEVATIONS CHANGE OR ARE INTERRUPTED BY ARCHITECTURAL ELEMENTS (CASED OPENINGS, ARCHWAYS, SKYLIGHT WELLS, ETC.) . D.SMOKE DETECTORS SHALL BE LISTED AND COMPLY WITH UL 217 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. BATHROOM: A.WATER CLOSETS SHALL BE LOCATED IN SPACES NOT LESS THAN 30" IN WIDTH AND 24" IN FRONT. B.WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT EXPOSURE TO WATER. CRC 702.3.7.1 C.BACKER FOR SHOWER AND TUB SHOWER WALLS TO BE FIBER-CEMENT, FIBER REINFORCED CEMENTITIOUS BACKER UNITS, GLASS MAT GYPSUM BACKERS OR FIBER-REINFORCED GYPSUM BACKERS TO A MIN HEIGHT OF 72" ABOVE THE FLOOR. D.USE 2X8 WOODEN BACKING IN ALL BATHROOM WALLS AT WATER CLOSET SHOWER AND BATHTUB, LOCATED AT 34" FROM FLOOR TO CENTER OF THE BACKING SUITABLE FOR THE ADDITION OF GRAB BARS. E.DOORS AND PANELS OF TUB AND SHOWER ENCLOSURES SHALL BE FULLY TEMPERED LAMINATED SAFETY GLASS OR APPROVED PLASTIC. F.SHOWER COMPARTMENTS SHALL HAVE MIN INTERIOR FLOOR AREA OF 1024 SQ IN AND ABLE TO CONTAIN A 30" DIA. CIRCLE. G.SHOWER AND TUB SHOWER COMBINATION IN ALL BUILDING SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. CARBON MONOXIDE ALARMS: CARBON MONOXIDE ALARMS REQUIRED BY SECTION 420.6.2 SHALL BE INSTALLED AND MAINTAINED IN THE FOLLOWING LOCATIONS: A.OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOM (S). B.ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS. C.IN GROUP R-1 OCCUPANCIES; ON THE CEILING OF EVERY SLEEPING UNIT OR OTHER LOCATIONS WITHIN THE SLEEPING UNIT IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. D.CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH BATTERY BACK-UP. ALARM WIRING SHALL BE DIRECTLY CONNECTED TO THE PERMANENT BUILDING WIRING WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. E.WHERE MORE THAN ONE CARBON MONOXIDE ALARM IS REQUIRED TO BE INSTALLED WITHIN THE DWELLING UNIT OR WITHIN A SLEEPING UNIT, THE ALARM SHALL BE INTERCONNECTED IN A MANNER THAT ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. F.CARBON MONOXIDE ALARMS SHALL BE LISTED AND COMPLY WITH UL 2034 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. BATHROOM ELECTRICAL: A.PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER RECEPTACLES, LIGHTS, FANS, ETC. (EXCEPTION-WHERE THE CIRCUIT SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED). B.ALL BRANCH CIRCUITS TO BE PROTECTED BY GROUND FAULT CIRCUIT INTERRUPTER (GFCI). KITCHEN VENTILATION: WHERE COMBUSTION APPLIANCES OR SOLID-FUEL BURNING APPLIANCES ARE LOCATED INSIDE THE PRESSURE BOUNDARY, THE MAXIMUM ALLOWABLE NET EXHAUST FLOW OF THE TWO LARGEST EXHAUST FANS SHALL NOT EXCEED 15 CFM PER 100 SQ. FT. OF OCCUPIABLE SPACE, WHEN OPERATING AT FULL CAPACITY. IF THE DESIGNED TOTAL NET FLOW EXCEEDS THIS LIMIT, THE NET EXHAUST FLOW MUST BE REDUCED BY REDUCING THE EXHAUST FLOW OR PROVIDING COMPENSATING OUT-DOOR AIRFLOW (NOTE: IF MAKE-UP AIR FAN IS INSTALLED IT MUST BE ELECTRICALLY INTERLOCKED WITH THE LARGEST EXHAUST FAN)LAUNDRY ELECTRICAL: AALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT (AFCI) CIRCUIT INTERRUPTER AND GROUND FAULT (GFCI) CIRCUIT INTERRUPTER. BPROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE LAUNDRY RECEPTACLE OUTLET. CMINIMUM 30 AMP DEDICATED CIRCUIT FOR DRYER PER CEC 220.54. HIGH EFFICACY LIGHTING: A.ALL LIGHTING SHALL BE HIGH EFFICACY AS DEFINED BY CEC TABLE 150.0-A B.ALL PERMANENTLY INSTALLED SCREW-BASED LIGHT FIXTURES SHALL CONTAIN SCREW-BASED JA8 (JOINT APPENDIX 8) COMPLIANT LAMPS AND BE MARKED AS JA8-2019 OR JA8-2019-E. CEC 150.0(k)G C.ALL JA8 COMPLIANT LIGHT FIXTURES INSTALLED IN CEILING RECESSED DOWNLIGHTS, LED LUMINARIES WITH INTEGRAL SOURCES, PIN-BASED LED LAMPS, AND GU24 BASED LED LIGHT SOURCES SHALL BE CONTROLLED BY VACANCY SENSORS OR DIMMERS. D.AT LEAST ONE FIXTURE IN EACH BATHROOM, GARAGE, LAUNDRY ROOM, AND UTILITY ROOM SHALL BE CONTROLLED BY A VACANCY SENSOR. E.ALL LIGHTING SHALL BE SWITCHED SEPARATELY FROM EXHAUST FANS (EXCEPT FOR KITCHEN EXHAUST HOODS). F.ALL UNDER CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING SYSTEMS. G.GARAGE, LAUNDRY, AND UTILITY ROOMS: LIGHTING INSTALLED IN GARAGES, LAUNDRY, AND UTILITY ROOMS SHALL BE HIGH EFFICACY AND CONTROLLED BY VACANCY SENSORS. H.HIGH EFFICACY LIGHTING IS NOT REQUIRED IN CLOSETS OF LESS THAN 70 SF. I.OUTDOOR LIGHTING PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY AND CONTROLLED WITH A MANUAL ON/OFF SWITCH AND BY PHOTO CONTROL AND A MOTION SENSOR. PER ENERGY 110.9. J.ALL OTHER ROOMS: LIGHTING INSTALLED IN ALL OTHER ROOMS SHALL BE HIGH EFFICACY OR SHALL BE CONTROLLED BY EITHER DIMMERS OR VACANCY SENSORS. ATTIC/UNDERFLOOR INSTALLED FAU: A.UNIT SHALL BE ACCESSIBLE THROUGH AN OPENING AND PASSAGEWAY NOT LESS THAN THE LARGEST COMPONENT OF THE UNIT AND NOT LESS THAN 22"x30" B.THE DISTANCE FROM THE PASSAGEWAY ACCESS TO THE UNIT SHALL NOT EXCEED 20' C.THE WIDTH OF THE PASSAGEWAY SHALL BE UNOBSTRUCTED AND SHALL HAVE SOLID FLOORING NOT LESS THAN 24" WIDE FROM THE ENTRANCE OPENING TO THE UNIT. D.A LEVEL WORKING PLATFORM NOT LESS THAN 30" BY 30" SHALL BE PROVIDED IN FRONT OF THE SERVICE SIDE OF THE UNIT. E.A PERMANENT 120V RECEPTACLE OUTLET AND A LIGHTING FIXTURE SHALL BE INSTALLED NEAR THE UNIT. THE SWITCH CONTROLLING THE LIGHTING FIXTURE SHALL BE LOCATED AT THE ENTRANCE TO THE PASSAGEWAY. ELECTRIC VEHICLE (EV) CHARGING: ELECTRIC VEHICLE SUPPLY EQUIPMENT SHALL BE INSTALLED TO FACILITATE THE FUTURE INSTALLATION OF AN EV CHARGING DEVICE AND MUST COMPLY WITH THE FOLLOWING: A.A LISTED TRADE SIZE 1 RACEWAY SHALL BE INSTALLED TO ACCOMMODATE A DEDICATED 208/240-VOLT BRANCH CIRCUIT. THE RACEWAY SHALL ORIGINATE FROM THE MAIN SERVICE PANEL OR SUB PANEL AND TERMINATES INTO A LISTED CABINET, BOX,OR OTHER ENCLOSURE IN CLOSE PROXIMITY TO THE FUTURE CHARGING DEVICE. B.THE SERVICE PANEL AND/OR SUB PANEL SHALL PROVIDE CAPACITY TO INSTALL A 40-AMP MIN. BRANCH CIRCUIT AND SPACE RESERVED TO ACCOMMODATE A BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE. C.THE ELECTRICAL PANEL SCHEDULE SHALL IDENTIFY THE OVERCURRENT PROTECTIVE DEVICE SPACE RESERVED FOR FUTURE EV CHARGING AS "EV CAPABLE". D.THE RACEWAY TERMINATION LOCATION SHALL BE PERMANENTLY AND VISIBLY MARKED AS "EV CAPABLE". XXX/150(144) = XXX SQ.IN. NFVA REQUIREDXXX/2 = XXX SQ. FT. REQUIRED AT TOP XXX/300(144) = XXX SQ.IN. NFVA REQUIRED 1 FLOOR VENT UNIT: 13.5" X 7.5" = 101.25 SQ.IN. NFVA 1 ROOF VENT UNIT, O'HAGIN OR EQUIV.: = 72 SQ.IN. NFVA X FLOOR VENTS PROVIDED, DISTRIBUTED EVENLY: (X) x 101.25 SQ.IN = XXX SQ.IN. NFVA XXX SQ.IN. NFVA PROVIDED > XXX SQ.IN. NFVA REQUIRED X ROOF VENTS PROVIDED, DISTRIBUTED EVENLY: (X) x 72 SQ.IN. = XXX SQ.IN. NFVA XXX SQ.IN. NFVA PROVIDED > XXX SQ.IN. NFVA REQUIRED FLOOR VENTILATION NEW UNDER FLOOR AREA TO BE VENTED = XXX SQ.FT. XXX' LINEAL FEET OF EAVE W/2X RAFTERS @ 24" O.C.: XXX'/24" = ±XXX AVAILABLE BLOCKS ATTIC VENTILATION NEW ATTIC AREA TO BE VENTED = XXX SQ.FT. XXX/2 = XXX SQ. FT. REQUIRED AT EAVE XXX/300(144) = XXX SQ.IN. NFVA REQUIRED 1 EAVE BLOCKING VENT UNIT: 16" x 4" = 28 SQ.IN. NFVA X EAVE VENTS PROVIDED, DISTRIBUTED EVENLY: (X) x 28 SQ.IN. = XXX SQ.IN. NFVA XXX SQ.IN. NFVA PROVIDED > XXX SQ.IN. NFVA REQUIRED AS SHOWN 1 Scale: 1/4"=1'-0" EXISTING BASEMENT FLOOR PLAN LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED 15 LIGHT-WELLDN DN 11058126832681268 41159FX80310 30682446FX2446FX2446FX2446FX2446FX606830682068 6068 2068 24310DH2630DH2630DH21033DH21033DH36703033DH4046DC4046DC4070 2330SC 2330SC 2330SC 2030SC 3068 2646SC 10446 1044612068226826686068 27682668 2668 2768507026682068 2668 2668UP UP UP UP 2646SC 1 A3.1 2 A3.1 3 A3.1 4 A3.1 F.C. 8'-9" ENTRY F.C. 8'-9" KITCHEN DINING BATH BEDROOMCLO.BATH HALLWAY FORMAL DINING V.I.F.V.I.F.V.I.F. LIVING LIBRARYFP CLO. LIGHT-WELL LIGHT-WELLLIGHT-WELLLIGHT WELL DECK DECK DECK UP UP UP UP (E) POST TO BE REMOVED (E) ELEC. METER EXISTING FLOOR PLANSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A2.2DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED 1 Scale: 1/4"=1'-0" EXISTING FIRST FLOOR PLAN 16 DN 26683030DC 510310 510310 2668 30687103102668 30682868 2368256826682668 23310SC23310FX23310SC23310SC23310SC23310SC23310SC2630SC86682568 1 A3.1 2 A3.1 3 A3.1 4 A3.1 CLO. F.C. 7'-10" F.C. 7'-11" F.F. - 1" F.C. 7'-10" PONY WALL SHOWER CURB MASTER BATH MASTER BDRM BUILT-IN CABS CLOSET CLOSET W.C. DN SHOWER CURB BATH BALCONY BEDROOM CLOSET OFFICE CLOSET NOOK FIRST FLR. OUTLINE FIRST FLR. OUTLINE BUILT-IN CABS ATTIC (E) SUB-PANEL EXISTING FLOOR PLANSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A2.3DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED 1 Scale: 1/4"=1'-0" EXISTING SECOND FLOOR PLAN 17 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2"1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2"1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2"1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2"EXISTING ELEVATIONSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A3.1DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN 1 Scale: 1/4"=1'-0" EXISTING FRONT ELEVATION 2 Scale: 1/4"=1'-0" EXISTING RIGHT ELEVATION 3 Scale: 1/4"=1'-0" EXISTING REAR ELEVATION 4 Scale: 1/4"=1'-0" EXISTING LEFT ELEVATION 18 LIGHT-WELLDN DN W01 W03 D02 W02 D06 D03 D04 D05 D01 D06 D06 UP UP UP HE HE HEHE HE HE HEHE HEHE 3 3 AFCI AFCI AFCI AFCI AFCI AFCI AFCI AFCI HE HE HEHE 3 3 AFCI AFCI AFCI HE HE HE HE HE HE HE HEHEHE 3 3 GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCIGFCIGFCI HE GFCI GFCI GFCI HE HE HE HE CO/SD CO/SD HEHE 3 3 AFCI HE GFCI HE HE HEHE HE HE GFCI AFCI AFCI AFCI AFCI AFCIAFCI AFCI 1 A5.1 2 A5.1 3 A5.1 4 A5.1 1 A6.1 1 A6.1 2 A6.1 2 A6.1 2'-4 1/2"10'-6" CL 5'-1 1/4" 2'-4 1/2"6'-1 1/2"CL 3'-2 1/2"5'-4 1/2"3'-6"3'-6" F.C. 8'-9" F.C. 8'-9" GUEST BEDROOM HALLWAY FORMAL DINING LIVING LIBRARYFP LIGHT-WELL LIGHT-WELLLIGHT-WELLLIGHT WELL DECK DECK UP UP UP NO CHANGES NO CHANGES NO CHANGES NO CHANGES CLOSET (N) FPLIVING UTILITY REFPANTRY KITCHEN UP BATH BATH VESTIBULE ENTRY DED. TO REF. DED. TO RANGE DED. TO HOOD DED. TO GD DW DED. TO DW DESK V VDED. TO FP GAS SUPPLY & SHUTOFF UP DOOR SCHEDULE - FIRST FLOOR NUMBER QTY FLOOR WIDTH HEIGHT TEMPERED DESCRIPTION D01 1 1 93 9/16 "80 "MULLED UNIT D02 1 1 30 "80 "YES EXT. HINGED- DOOR F01 D03 1 1 144 "80 "YES EXT. QUAD SLIDER-GLASS PANEL D04 1 1 96 "80 "SLIDER-DOOR P04 D05 1 1 30 "80 "POCKET-DOOR P04 D06 3 1 30 "80 "HINGED-DOOR P04 DOOR SCHEDULE - SECOND FLOOR WINDOW SCHEDULE - FIRST FLOOR NUMBER QTY FLOOR WIDTH HEIGHT DESCRIPTION BOTTOM EGRESS TEMPERED W01 1 1 59 "69 "FIXED GLASS 11" W02 1 1 36 "36 "DOUBLE HUNG 44" W03 1 1 60 "36 " TRIPLE CASEMENT-LHL/ RHR 44" WINDOW SCHEDULE - SECOND FLOOR PROPOSED FLOOR PLANSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A4.1DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN 1 Scale: 1/4"=1'-0" PROPOSED FIRST FLOOR PLAN LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED NEW INTERIOR CONSTRUCTION; 2x4 WD. STUD, 1/2" GYP. BD. EACH SIDE NEW EXTERIOR CONSTRUCTION NEW 1-HR FIRE RATED WALL; 2x4 WD. STUD, 5/8" TYPE "X" GYP. BD. EACH SIDE. SEE PLAN FOR LOCATIONS. LAUNDRY/BATHROOM VENTILATION: FOR LAUNDRY ROOMS AND BATHROOMS WITHOUT AN OPERABLE WINDOW: A.PROVIDE MECHANICAL VENTILATION SYSTEM CAPABLE OF 5 AIR CHANGES/HR. TO EXTERIOR. B.USE SMOOTH METAL DUCT FOR DRYER EXHAUST WITH A MAX. LENGTH OF 14', TO OUTSIDE WITH BACKDRAFT DAMPER AND TWO 90° ELBOWS AND A MIN. OF 4" DIA. C.TERMINATION OF ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MINIMUM OF 3 FEET FROM PROPERTY LINES OR ANY OPENINGS INTO THE BUILDING (i.e., DRYERS, BATH AND UTILITY FANS, ETC., MUST BE 3 FEET AWAY FROM DOORS WINDOWS, OPENING SKYLIGHTS OR ATTIC VENTS). D.EXHAUST FANS SHALL HAVE A MIN. OF 50 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR CONTINUOUS VENTILATION AND BE ENERGYSTAR COMPLIANT AND BE EQUIPPED WITH A HUMIDISTAT AND HUMIDITY CONTROL. AND BE SWITCHED SEPARATELY FROM LIGHTING SYSTEM. PLUMBING: A.ALL NEW TOILETS SHALL HAVE AN EFFECTIVE FLUSH VOLUME NOT TO EXCEED 1.28 GALLONS PER FLUSH. B.ALL NEW LAVATORY FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.2 GALLONS PER MINUTE AT 60 PSI. C.ALL NEW SHOWERHEADS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. D.MULTIPLE SHOWERHEADS SERVING ONE SHOWER - COMBINED FLOW RATE OF ALL SHOWERHEADS AND/OR OTHER SHOWER OUTLETS CONTROLLED BY A SINGLE VALVE SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. E.ALL NEW KITCHEN FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN FAUCETS MAY TEMPORARILY INCREASE THE FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER MINUTE AT 60 PSI AND MUST DEFAULT TO A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN ELECTRICAL: A.ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER(AFCI). B.PROVIDE AFCI AND GFCI PROTECTION AT ALL RECEPTACLES SERVING KITCHEN COUNTERTOPS. C.AT EACH KITCHEN AND DINING AREA COUNTER SPACE WIDER THAN 12", LOCATE A RECEPTACLE SO THAT NO POINT ALONG THE COUNTER WALL IS OVER 24" FROM A RECEPTACLE. COUNTERTOP RECEPTACLES REQUIRED WITHIN 24" EACH SIDE OF A BREAK IN THE CONTINUOUS COUNTERTOP SURFACE (SINKS-STOVES). D.REQ'D RECEPTACLES MOUNTED ON THE SIDES OF CABINETS SHALL BE A MAXIMUM OF 12" BELOW THE COUNTERTOP SURFACE WITH A MAXIMUM OF 6" COUNTERTOP OVERHANG. E.PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS FOR COUNTER RECEPTACLES. SMOKE DETECTORS: A.SMOKE DETECTOR SYSTEM SHALL BE HARD WIRED, INTERCONNECTED TO SOUND SIMULTANEOUSLY AND EQUIPPED WITH BATTERY BACKUP. B.INSTALL DETECTORS IN EACH BEDROOM, AT EACH CORRIDOR/AREA NEXT TO THE BEDROOM, AT THE TOP OF STAIRS AND EACH STORY AND BASEMENT. C.MULTIPLE SMOKE DETECTORS ARE REQUIRED WHEN CEILING LEVELS/ ELEVATIONS CHANGE OR ARE INTERRUPTED BY ARCHITECTURAL ELEMENTS (CASED OPENINGS, ARCHWAYS, SKYLIGHT WELLS, ETC.) . D.SMOKE DETECTORS SHALL BE LISTED AND COMPLY WITH UL 217 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. BATHROOM: A.WATER CLOSETS SHALL BE LOCATED IN SPACES NOT LESS THAN 30" IN WIDTH AND 24" IN FRONT. B.WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT EXPOSURE TO WATER. CRC 702.3.7.1 C.BACKER FOR SHOWER AND TUB SHOWER WALLS TO BE FIBER-CEMENT, FIBER REINFORCED CEMENTITIOUS BACKER UNITS, GLASS MAT GYPSUM BACKERS OR FIBER-REINFORCED GYPSUM BACKERS TO A MIN HEIGHT OF 72" ABOVE THE FLOOR. D.USE 2X8 WOODEN BACKING IN ALL BATHROOM WALLS AT WATER CLOSET SHOWER AND BATHTUB, LOCATED AT 34" FROM FLOOR TO CENTER OF THE BACKING SUITABLE FOR THE ADDITION OF GRAB BARS. E.DOORS AND PANELS OF TUB AND SHOWER ENCLOSURES SHALL BE FULLY TEMPERED LAMINATED SAFETY GLASS OR APPROVED PLASTIC. F.SHOWER COMPARTMENTS SHALL HAVE MIN INTERIOR FLOOR AREA OF 1024 SQ IN AND ABLE TO CONTAIN A 30" DIA. CIRCLE. G.SHOWER AND TUB SHOWER COMBINATION IN ALL BUILDING SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. CARBON MONOXIDE ALARMS: CARBON MONOXIDE ALARMS REQUIRED BY SECTION 420.6.2 SHALL BE INSTALLED AND MAINTAINED IN THE FOLLOWING LOCATIONS: A.OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOM (S). B.ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS. C.IN GROUP R-1 OCCUPANCIES; ON THE CEILING OF EVERY SLEEPING UNIT OR OTHER LOCATIONS WITHIN THE SLEEPING UNIT IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. D.CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH BATTERY BACK-UP. ALARM WIRING SHALL BE DIRECTLY CONNECTED TO THE PERMANENT BUILDING WIRING WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. E.WHERE MORE THAN ONE CARBON MONOXIDE ALARM IS REQUIRED TO BE INSTALLED WITHIN THE DWELLING UNIT OR WITHIN A SLEEPING UNIT, THE ALARM SHALL BE INTERCONNECTED IN A MANNER THAT ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. F.CARBON MONOXIDE ALARMS SHALL BE LISTED AND COMPLY WITH UL 2034 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. BATHROOM ELECTRICAL: A.PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER RECEPTACLES, LIGHTS, FANS, ETC. (EXCEPTION-WHERE THE CIRCUIT SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED). B.ALL BRANCH CIRCUITS TO BE PROTECTED BY GROUND FAULT CIRCUIT INTERRUPTER (GFCI). KITCHEN VENTILATION: WHERE COMBUSTION APPLIANCES OR SOLID-FUEL BURNING APPLIANCES ARE LOCATED INSIDE THE PRESSURE BOUNDARY, THE MAXIMUM ALLOWABLE NET EXHAUST FLOW OF THE TWO LARGEST EXHAUST FANS SHALL NOT EXCEED 15 CFM PER 100 SQ. FT. OF OCCUPIABLE SPACE, WHEN OPERATING AT FULL CAPACITY. IF THE DESIGNED TOTAL NET FLOW EXCEEDS THIS LIMIT, THE NET EXHAUST FLOW MUST BE REDUCED BY REDUCING THE EXHAUST FLOW OR PROVIDING COMPENSATING OUT-DOOR AIRFLOW (NOTE: IF MAKE-UP AIR FAN IS INSTALLED IT MUST BE ELECTRICALLY INTERLOCKED WITH THE LARGEST EXHAUST FAN) LAUNDRY ELECTRICAL: AALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT (AFCI) CIRCUIT INTERRUPTER AND GROUND FAULT (GFCI) CIRCUIT INTERRUPTER. BPROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE LAUNDRY RECEPTACLE OUTLET. CMINIMUM 30 AMP DEDICATED CIRCUIT FOR DRYER PER CEC 220.54. HIGH EFFICACY LIGHTING: A.ALL LIGHTING SHALL BE HIGH EFFICACY AS DEFINED BY CEC TABLE 150.0-A B.ALL PERMANENTLY INSTALLED SCREW-BASED LIGHT FIXTURES SHALL CONTAIN SCREW-BASED JA8 (JOINT APPENDIX 8) COMPLIANT LAMPS AND BE MARKED AS JA8-2019 OR JA8-2019-E. CEC 150.0(k)G C.ALL JA8 COMPLIANT LIGHT FIXTURES INSTALLED IN CEILING RECESSED DOWNLIGHTS, LED LUMINARIES WITH INTEGRAL SOURCES, PIN-BASED LED LAMPS, AND GU24 BASED LED LIGHT SOURCES SHALL BE CONTROLLED BY VACANCY SENSORS OR DIMMERS. D.AT LEAST ONE FIXTURE IN EACH BATHROOM, GARAGE, LAUNDRY ROOM, AND UTILITY ROOM SHALL BE CONTROLLED BY A VACANCY SENSOR. E.ALL LIGHTING SHALL BE SWITCHED SEPARATELY FROM EXHAUST FANS (EXCEPT FOR KITCHEN EXHAUST HOODS). F.ALL UNDER CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING SYSTEMS. G.GARAGE, LAUNDRY, AND UTILITY ROOMS: LIGHTING INSTALLED IN GARAGES, LAUNDRY, AND UTILITY ROOMS SHALL BE HIGH EFFICACY AND CONTROLLED BY VACANCY SENSORS. H.HIGH EFFICACY LIGHTING IS NOT REQUIRED IN CLOSETS OF LESS THAN 70 SF. I.OUTDOOR LIGHTING PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY AND CONTROLLED WITH A MANUAL ON/OFF SWITCH AND BY PHOTO CONTROL AND A MOTION SENSOR. PER ENERGY 110.9. J.ALL OTHER ROOMS: LIGHTING INSTALLED IN ALL OTHER ROOMS SHALL BE HIGH EFFICACY OR SHALL BE CONTROLLED BY EITHER DIMMERS OR VACANCY SENSORS. ATTIC/UNDERFLOOR INSTALLED FAU: A.UNIT SHALL BE ACCESSIBLE THROUGH AN OPENING AND PASSAGEWAY NOT LESS THAN THE LARGEST COMPONENT OF THE UNIT AND NOT LESS THAN 22"x30" B.THE DISTANCE FROM THE PASSAGEWAY ACCESS TO THE UNIT SHALL NOT EXCEED 20' C.THE WIDTH OF THE PASSAGEWAY SHALL BE UNOBSTRUCTED AND SHALL HAVE SOLID FLOORING NOT LESS THAN 24" WIDE FROM THE ENTRANCE OPENING TO THE UNIT. D.A LEVEL WORKING PLATFORM NOT LESS THAN 30" BY 30" SHALL BE PROVIDED IN FRONT OF THE SERVICE SIDE OF THE UNIT. E.A PERMANENT 120V RECEPTACLE OUTLET AND A LIGHTING FIXTURE SHALL BE INSTALLED NEAR THE UNIT. THE SWITCH CONTROLLING THE LIGHTING FIXTURE SHALL BE LOCATED AT THE ENTRANCE TO THE PASSAGEWAY. ELECTRIC VEHICLE (EV) CHARGING: ELECTRIC VEHICLE SUPPLY EQUIPMENT SHALL BE INSTALLED TO FACILITATE THE FUTURE INSTALLATION OF AN EV CHARGING DEVICE AND MUST COMPLY WITH THE FOLLOWING: A.A LISTED TRADE SIZE 1 RACEWAY SHALL BE INSTALLED TO ACCOMMODATE A DEDICATED 208/240-VOLT BRANCH CIRCUIT. THE RACEWAY SHALL ORIGINATE FROM THE MAIN SERVICE PANEL OR SUB PANEL AND TERMINATES INTO A LISTED CABINET, BOX,OR OTHER ENCLOSURE IN CLOSE PROXIMITY TO THE FUTURE CHARGING DEVICE. B.THE SERVICE PANEL AND/OR SUB PANEL SHALL PROVIDE CAPACITY TO INSTALL A 40-AMP MIN. BRANCH CIRCUIT AND SPACE RESERVED TO ACCOMMODATE A BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE. C.THE ELECTRICAL PANEL SCHEDULE SHALL IDENTIFY THE OVERCURRENT PROTECTIVE DEVICE SPACE RESERVED FOR FUTURE EV CHARGING AS "EV CAPABLE". D.THE RACEWAY TERMINATION LOCATION SHALL BE PERMANENTLY AND VISIBLY MARKED AS "EV CAPABLE". TYPICAL NOTES: LAUNDRY/BATHROOM VENTILATION: FOR LAUNDRY ROOMS AND BATHROOMS WITHOUT AN OPERABLE WINDOW: A.PROVIDE MECHANICAL VENTILATION SYSTEM CAPABLE OF 5 AIR CHANGES/HR. TO EXTERIOR. B.USE SMOOTH METAL DUCT FOR DRYER EXHAUST WITH A MAX. LENGTH OF 14', TO OUTSIDE WITH BACKDRAFT DAMPER AND TWO 90° ELBOWS AND A MIN. OF 4" DIA. C.TERMINATION OF ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MINIMUM OF 3 FEET FROM PROPERTY LINES OR ANY OPENINGS INTO THE BUILDING (i.e., DRYERS, BATH AND UTILITY FANS, ETC., MUST BE 3 FEET AWAY FROM DOORS WINDOWS, OPENING SKYLIGHTS OR ATTIC VENTS). D.EXHAUST FANS SHALL HAVE A MIN. OF 50 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR CONTINUOUS VENTILATION AND BE ENERGYSTAR COMPLIANT AND BE EQUIPPED WITH A HUMIDISTAT AND HUMIDITY CONTROL. AND BE SWITCHED SEPARATELY FROM LIGHTING SYSTEM. KITCHEN ELECTRICAL: A.ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER(AFCI). B.PROVIDE AFCI AND GFCI PROTECTION AT ALL RECEPTACLES SERVING KITCHEN COUNTERTOPS. C.AT EACH KITCHEN AND DINING AREA COUNTER SPACE WIDER THAN 12", LOCATE A RECEPTACLE SO THAT NO POINT ALONG THE COUNTER WALL IS OVER 24" FROM A RECEPTACLE. COUNTERTOP RECEPTACLES REQUIRED WITHIN 24" EACH SIDE OF A BREAK IN THE CONTINUOUS COUNTERTOP SURFACE (SINKS-STOVES). D.REQ'D RECEPTACLES MOUNTED ON THE SIDES OF CABINETS SHALL BE A MAXIMUM OF 12" BELOW THE COUNTERTOP SURFACE WITH A MAXIMUM OF 6" COUNTERTOP OVERHANG. E.PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS FOR COUNTER RECEPTACLES. BATHROOM ELECTRICAL: A.PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER RECEPTACLES, LIGHTS, FANS, ETC. (EXCEPTION-WHERE THE CIRCUIT SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED). B.ALL BRANCH CIRCUITS TO BE PROTECTED BY GROUND FAULT CIRCUIT INTERRUPTER (GFCI). LAUNDRY ELECTRICAL: A ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT (AFCI) CIRCUIT INTERRUPTER AND GROUND FAULT (GFCI) CIRCUIT INTERRUPTER. B PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE LAUNDRY RECEPTACLE OUTLET. C MINIMUM 30 AMP DEDICATED CIRCUIT FOR DRYER PER CEC 220.54. HIGH EFFICACY LIGHTING: A.ALL LIGHTING SHALL BE HIGH EFFICACY AS DEFINED BY CEC TABLE 150.0-A B.ALL PERMANENTLY INSTALLED SCREW-BASED LIGHT FIXTURES SHALL CONTAIN SCREW-BASED JA8 (JOINT APPENDIX 8) COMPLIANT LAMPS AND BE MARKED AS JA8-2019 OR JA8-2019-E. CEC 150.0(k)G C.ALL JA8 COMPLIANT LIGHT FIXTURES INSTALLED IN CEILING RECESSED DOWNLIGHTS, LED LUMINARIES WITH INTEGRAL SOURCES, PIN-BASED LED LAMPS, AND GU24 BASED LED LIGHT SOURCES SHALL BE CONTROLLED BY VACANCY SENSORS OR DIMMERS. D.AT LEAST ONE FIXTURE IN EACH BATHROOM, GARAGE, LAUNDRY ROOM, AND UTILITY ROOM SHALL BE CONTROLLED BY A VACANCY SENSOR. E.ALL LIGHTING SHALL BE SWITCHED SEPARATELY FROM EXHAUST FANS (EXCEPT FOR KITCHEN EXHAUST HOODS). F.ALL UNDER CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING SYSTEMS. G.GARAGE, LAUNDRY, AND UTILITY ROOMS: LIGHTING INSTALLED IN GARAGES, LAUNDRY, AND UTILITY ROOMS SHALL BE HIGH EFFICACY AND CONTROLLED BY VACANCY SENSORS. H.HIGH EFFICACY LIGHTING IS NOT REQUIRED IN CLOSETS OF LESS THAN 70 SF. I.OUTDOOR LIGHTING PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY AND CONTROLLED WITH A MANUAL ON/OFF SWITCH AND BY PHOTO CONTROL AND A MOTION SENSOR. PER ENERGY 110.9. J.ALL OTHER ROOMS: LIGHTING INSTALLED IN ALL OTHER ROOMS SHALL BE HIGH EFFICACY OR SHALL BE CONTROLLED BY EITHER DIMMERS OR VACANCY SENSORS. PLUMBING: A.ALL NEW TOILETS SHALL HAVE AN EFFECTIVE FLUSH VOLUME NOT TO EXCEED 1.28 GALLONS PER FLUSH. B.ALL NEW LAVATORY FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.2 GALLONS PER MINUTE AT 60 PSI. C.ALL NEW SHOWERHEADS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. D.MULTIPLE SHOWERHEADS SERVING ONE SHOWER - COMBINED FLOW RATE OF ALL SHOWERHEADS AND/OR OTHER SHOWER OUTLETS CONTROLLED BY A SINGLE VALVE SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. E.ALL NEW KITCHEN FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN FAUCETS MAY TEMPORARILY INCREASE THE FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER MINUTE AT 60 PSI AND MUST DEFAULT TO A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. BATHROOM: A.WATER CLOSETS SHALL BE LOCATED IN SPACES NOT LESS THAN 30" IN WIDTH AND 24" IN FRONT. B.WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT EXPOSURE TO WATER. CRC 702.3.7.1 C.BACKER FOR SHOWER AND TUB SHOWER WALLS TO BE FIBER-CEMENT, FIBER REINFORCED CEMENTITIOUS BACKER UNITS, GLASS MAT GYPSUM BACKERS OR FIBER-REINFORCED GYPSUM BACKERS TO A MIN HEIGHT OF 72" ABOVE THE FLOOR. D.USE 2X8 WOODEN BACKING IN ALL BATHROOM WALLS AT WATER CLOSET SHOWER AND BATHTUB, LOCATED AT 34" FROM FLOOR TO CENTER OF THE BACKING SUITABLE FOR THE ADDITION OF GRAB BARS. E.DOORS AND PANELS OF TUB AND SHOWER ENCLOSURES SHALL BE FULLY TEMPERED LAMINATED SAFETY GLASS OR APPROVED PLASTIC. F.SHOWER COMPARTMENTS SHALL HAVE MIN INTERIOR FLOOR AREA OF 1024 SQ IN AND ABLE TO CONTAIN A 30" DIA. CIRCLE. G.SHOWER AND TUB SHOWER COMBINATION IN ALL BUILDING SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. ELECTRICAL LEGEND (ALL LIGHTING TO BE HIGH EFFICACY) AFCI GFCI WP SMOKE DETECTORS: A.SMOKE DETECTOR SYSTEM SHALL BE HARD WIRED, INTERCONNECTED TO SOUND SIMULTANEOUSLY AND EQUIPPED WITH BATTERY BACKUP. B.INSTALL DETECTORS IN EACH BEDROOM, AT EACH CORRIDOR/AREA NEXT TO THE BEDROOM, AT THE TOP OF STAIRS AND EACH STORY AND BASEMENT. C.MULTIPLE SMOKE DETECTORS ARE REQUIRED WHEN CEILING LEVELS/ ELEVATIONS CHANGE OR ARE INTERRUPTED BY ARCHITECTURAL ELEMENTS (CASED OPENINGS, ARCHWAYS, SKYLIGHT WELLS, ETC.) . D.SMOKE DETECTORS SHALL BE LISTED AND COMPLY WITH UL 217 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. CARBON MONOXIDE ALARMS: CARBON MONOXIDE ALARMS REQUIRED BY SECTION 420.6.2 SHALL BE INSTALLED AND MAINTAINED IN THE FOLLOWING LOCATIONS: A.OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOM (S). B.ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS. C.IN GROUP R-1 OCCUPANCIES; ON THE CEILING OF EVERY SLEEPING UNIT OR OTHER LOCATIONS WITHIN THE SLEEPING UNIT IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. D.CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH BATTERY BACK-UP. ALARM WIRING SHALL BE DIRECTLY CONNECTED TO THE PERMANENT BUILDING WIRING WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. E.WHERE MORE THAN ONE CARBON MONOXIDE ALARM IS REQUIRED TO BE INSTALLED WITHIN THE DWELLING UNIT OR WITHIN A SLEEPING UNIT, THE ALARM SHALL BE INTERCONNECTED IN A MANNER THAT ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. F.CARBON MONOXIDE ALARMS SHALL BE LISTED AND COMPLY WITH UL 2034 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. KITCHEN VENTILATION: WHERE COMBUSTION APPLIANCES OR SOLID-FUEL BURNING APPLIANCES ARE LOCATED INSIDE THE PRESSURE BOUNDARY, THE MAXIMUM ALLOWABLE NET EXHAUST FLOW OF THE TWO LARGEST EXHAUST FANS SHALL NOT EXCEED 15 CFM PER 100 SQ. FT. OF OCCUPIABLE SPACE, WHEN OPERATING AT FULL CAPACITY. IF THE DESIGNED TOTAL NET FLOW EXCEEDS THIS LIMIT, THE NET EXHAUST FLOW MUST BE REDUCED BY REDUCING THE EXHAUST FLOW OR PROVIDING COMPENSATING OUT-DOOR AIRFLOW (NOTE: IF MAKE-UP AIR FAN IS INSTALLED IT MUST BE ELECTRICALLY INTERLOCKED WITH THE LARGEST EXHAUST FAN) ATTIC/UNDERFLOOR INSTALLED FAU: A.UNIT SHALL BE ACCESSIBLE THROUGH AN OPENING AND PASSAGEWAY NOT LESS THAN THE LARGEST COMPONENT OF THE UNIT AND NOT LESS THAN 22"x30" B.THE DISTANCE FROM THE PASSAGEWAY ACCESS TO THE UNIT SHALL NOT EXCEED 20' C.THE WIDTH OF THE PASSAGEWAY SHALL BE UNOBSTRUCTED AND SHALL HAVE SOLID FLOORING NOT LESS THAN 24" WIDE FROM THE ENTRANCE OPENING TO THE UNIT. D.A LEVEL WORKING PLATFORM NOT LESS THAN 30" BY 30" SHALL BE PROVIDED IN FRONT OF THE SERVICE SIDE OF THE UNIT. E.A PERMANENT 120V RECEPTACLE OUTLET AND A LIGHTING FIXTURE SHALL BE INSTALLED NEAR THE UNIT. THE SWITCH CONTROLLING THE LIGHTING FIXTURE SHALL BE LOCATED AT THE ENTRANCE TO THE PASSAGEWAY. TYPICAL NOTES: LAUNDRY/BATHROOM VENTILATION: FOR LAUNDRY ROOMS AND BATHROOMS WITHOUT AN OPERABLE WINDOW: A.PROVIDE MECHANICAL VENTILATION SYSTEM CAPABLE OF 5 AIR CHANGES/HR. TO EXTERIOR. B.USE SMOOTH METAL DUCT FOR DRYER EXHAUST WITH A MAX. LENGTH OF 14', TO OUTSIDE WITH BACKDRAFT DAMPER AND TWO 90° ELBOWS AND A MIN. OF 4" DIA. C.TERMINATION OF ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MINIMUM OF 3 FEET FROM PROPERTY LINES OR ANY OPENINGS INTO THE BUILDING (i.e., DRYERS, BATH AND UTILITY FANS, ETC., MUST BE 3 FEET AWAY FROM DOORS WINDOWS, OPENING SKYLIGHTS OR ATTIC VENTS). D.EXHAUST FANS SHALL HAVE A MIN. OF 50 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR CONTINUOUS VENTILATION AND BE ENERGYSTAR COMPLIANT AND BE EQUIPPED WITH A HUMIDISTAT AND HUMIDITY CONTROL. AND BE SWITCHED SEPARATELY FROM LIGHTING SYSTEM. KITCHEN ELECTRICAL: A.ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER(AFCI). B.PROVIDE AFCI AND GFCI PROTECTION AT ALL RECEPTACLES SERVING KITCHEN COUNTERTOPS. C.AT EACH KITCHEN AND DINING AREA COUNTER SPACE WIDER THAN 12", LOCATE A RECEPTACLE SO THAT NO POINT ALONG THE COUNTER WALL IS OVER 24" FROM A RECEPTACLE. COUNTERTOP RECEPTACLES REQUIRED WITHIN 24" EACH SIDE OF A BREAK IN THE CONTINUOUS COUNTERTOP SURFACE (SINKS-STOVES). D.REQ'D RECEPTACLES MOUNTED ON THE SIDES OF CABINETS SHALL BE A MAXIMUM OF 12" BELOW THE COUNTERTOP SURFACE WITH A MAXIMUM OF 6" COUNTERTOP OVERHANG. E.PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS FOR COUNTER RECEPTACLES. BATHROOM ELECTRICAL: A.PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER RECEPTACLES, LIGHTS, FANS, ETC. (EXCEPTION-WHERE THE CIRCUIT SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED). B.ALL BRANCH CIRCUITS TO BE PROTECTED BY GROUND FAULT CIRCUIT INTERRUPTER (GFCI). LAUNDRY ELECTRICAL: A ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT (AFCI) CIRCUIT INTERRUPTER AND GROUND FAULT (GFCI) CIRCUIT INTERRUPTER. B PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE LAUNDRY RECEPTACLE OUTLET. C MINIMUM 30 AMP DEDICATED CIRCUIT FOR DRYER PER CEC 220.54. HIGH EFFICACY LIGHTING: A.ALL LIGHTING SHALL BE HIGH EFFICACY AS DEFINED BY CEC TABLE 150.0-A B.ALL PERMANENTLY INSTALLED SCREW-BASED LIGHT FIXTURES SHALL CONTAIN SCREW-BASED JA8 (JOINT APPENDIX 8) COMPLIANT LAMPS AND BE MARKED AS JA8-2019 OR JA8-2019-E. CEC 150.0(k)G C.ALL JA8 COMPLIANT LIGHT FIXTURES INSTALLED IN CEILING RECESSED DOWNLIGHTS, LED LUMINARIES WITH INTEGRAL SOURCES, PIN-BASED LED LAMPS, AND GU24 BASED LED LIGHT SOURCES SHALL BE CONTROLLED BY VACANCY SENSORS OR DIMMERS. D.AT LEAST ONE FIXTURE IN EACH BATHROOM, GARAGE, LAUNDRY ROOM, AND UTILITY ROOM SHALL BE CONTROLLED BY A VACANCY SENSOR. E.ALL LIGHTING SHALL BE SWITCHED SEPARATELY FROM EXHAUST FANS (EXCEPT FOR KITCHEN EXHAUST HOODS). F.ALL UNDER CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING SYSTEMS. G.GARAGE, LAUNDRY, AND UTILITY ROOMS: LIGHTING INSTALLED IN GARAGES, LAUNDRY, AND UTILITY ROOMS SHALL BE HIGH EFFICACY AND CONTROLLED BY VACANCY SENSORS. H.HIGH EFFICACY LIGHTING IS NOT REQUIRED IN CLOSETS OF LESS THAN 70 SF. I.OUTDOOR LIGHTING PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY AND CONTROLLED WITH A MANUAL ON/OFF SWITCH AND BY PHOTO CONTROL AND A MOTION SENSOR. PER ENERGY 110.9. J.ALL OTHER ROOMS: LIGHTING INSTALLED IN ALL OTHER ROOMS SHALL BE HIGH EFFICACY OR SHALL BE CONTROLLED BY EITHER DIMMERS OR VACANCY SENSORS. PLUMBING: A.ALL NEW TOILETS SHALL HAVE AN EFFECTIVE FLUSH VOLUME NOT TO EXCEED 1.28 GALLONS PER FLUSH. B.ALL NEW LAVATORY FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.2 GALLONS PER MINUTE AT 60 PSI. C.ALL NEW SHOWERHEADS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. D.MULTIPLE SHOWERHEADS SERVING ONE SHOWER - COMBINED FLOW RATE OF ALL SHOWERHEADS AND/OR OTHER SHOWER OUTLETS CONTROLLED BY A SINGLE VALVE SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. E.ALL NEW KITCHEN FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN FAUCETS MAY TEMPORARILY INCREASE THE FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER MINUTE AT 60 PSI AND MUST DEFAULT TO A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. BATHROOM: A.WATER CLOSETS SHALL BE LOCATED IN SPACES NOT LESS THAN 30" IN WIDTH AND 24" IN FRONT. B.WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT EXPOSURE TO WATER. CRC 702.3.7.1 C.BACKER FOR SHOWER AND TUB SHOWER WALLS TO BE FIBER-CEMENT, FIBER REINFORCED CEMENTITIOUS BACKER UNITS, GLASS MAT GYPSUM BACKERS OR FIBER-REINFORCED GYPSUM BACKERS TO A MIN HEIGHT OF 72" ABOVE THE FLOOR. D.USE 2X8 WOODEN BACKING IN ALL BATHROOM WALLS AT WATER CLOSET SHOWER AND BATHTUB, LOCATED AT 34" FROM FLOOR TO CENTER OF THE BACKING SUITABLE FOR THE ADDITION OF GRAB BARS. E.DOORS AND PANELS OF TUB AND SHOWER ENCLOSURES SHALL BE FULLY TEMPERED LAMINATED SAFETY GLASS OR APPROVED PLASTIC. F.SHOWER COMPARTMENTS SHALL HAVE MIN INTERIOR FLOOR AREA OF 1024 SQ IN AND ABLE TO CONTAIN A 30" DIA. CIRCLE. G.SHOWER AND TUB SHOWER COMBINATION IN ALL BUILDING SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. ELECTRICAL LEGEND (ALL LIGHTING TO BE HIGH EFFICACY) AFCI GFCI WP DOOR SCHEDULE NOTES: 1.DO NOT ORDER DIRECTLY OFF THIS SCHEDULE. FIELD VERIFY ROUGH OPENINGS PRIOR TO PLACING ORDER. WHEN ALL ROUGH OPENINGS ARE FRAMED, NOTIFY PROJECT MANAGER AND OWNER SO THAT A WALKTHROUGH CAN BE SCHEDULED TO REVIEW OPENINGS AND DOOR OPERATION PRIOR TO PLACING DOOR ORDER. 2.ALL PANELS OF GLAZING IN DOORS TO BE TEMPERED. 3.VERIFY DOOR MANUF. AND FINISH WITH OWNER PRIOR TO PLACING ORDER. WINDOW SCHEDULE NOTES: 1.DO NOT ORDER DIRECTLY OFF THIS SCHEDULE. WINDOW MEASUREMENTS SHOWN ARE APPROXIMATE, THE INTENTS IS TO USE THE MANUF. STANDARDS SIZES WHEREVER POSSIBLE. WHERE ALL ROUGH OPENINGS ARE FRAMED, NOTIFY PROJECT MANAGER AND OWNER SO THAT WALKTROUGH CAN BE SCHEDULED TO REVIEW OPENINGS AND WINDOW OPERATION PRIOR PLACING WINDOW ORDER. 2.VERIFY CODE COMPLIANCE OF NOTED EGRESS WINDOWS WITH MANUF. PRIOR TO PLACING ORDER. WINDOWS MARKED "EGRESS" TO HAVE BOTTOM OF CLEAR OPENING NO MORE THAN 44" A.F.F.; MINIMUM NET CLEAR OPENABLE DIMENSIONS - HEIGHT: 24"; WIDTH: 20"; AREA: 5.7 SF. 3.SEE TITLE 24 DOCUMENTS FOR MAXIMUM U-FACTORS AND SHGC VALUES. CONTRACTOR NOT TO WASH WINDOWS OR REMOVE LABELS PRIOR TO INSPECTION AND VERIFICATION OF VALUES. HE EXHAUST FAN/EXHAUST FAN/LIGHT COMBO. SEE BATH ELECTRICAL NOTES, THIS PAGE. 'W' INDICATES CONTINUOUSLY OPERATING MULTI-SPEED WHOLE BUILDING VENTILATION FAN. SEE WHOLE BUILDING VENTILATION NOTES THIS PAGE. OUTDOOR LIGHT. EXTERIOR LIGHTING ATTACHED TO THE BUILDING SHALL BE HIGH EFFICACY WITH A MANUAL ON/OFF SWITCH AND CONTROLLED BY MOTION SENSOR & PHOTO CONTROL. FIXTURE SHALL BE DOWNWARD LIGHTING. SWITCH 3-WAY SWITCH SWITCH WITH VACANCY SENSOR. SWITCH WITH DIMMER TYP. 110 RECEPTACLE RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. ARC-FAULT CIRCUIT INTERRUPTER PROTECTED RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. WATERPROOF RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. PROVIDE EXTERIOR GFCI WATERPROOF RECEPTACLES AT THE FRONT & REAR OF RESIDENCE WITHIN 6'- 6" OF GRADE. SURFACE MOUNT WALL SCONCE. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. COMBINATION SMOKE DETECTOR AND CARBON MONOXIDE DETECTOR UNIT. SEE NOTES THIS PAGE CEILING OR FLOOR MOUNTED HVAC REGISTER. O.L. SD/ CO CHANDELIER VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. SURFACE MOUNT CEILING LIGHT FIXTURE OR PENDANT. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. HIGH EFFICACY RECESSED LIGHT FIXTURE. SEE HIGH EFFICACY LIGHTING NOTES THIS PAGE. LIGHTS IN INSULATED CEILINGS SHALL BE IC RATED, HAVE ELECTRONIC BALLAST AND BE AIR- TIGHT (AT). UNDER-CABINET FLUORESCENT LIGHT. SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING. 3 D V O.L. QUADRUPLEX RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. HE EXHAUST FAN/EXHAUST FAN/LIGHT COMBO. SEE BATH ELECTRICAL NOTES, THIS PAGE. 'W' INDICATES CONTINUOUSLY OPERATING MULTI-SPEED WHOLE BUILDING VENTILATION FAN. SEE WHOLE BUILDING VENTILATION NOTES THIS PAGE. OUTDOOR LIGHT. EXTERIOR LIGHTING ATTACHED TO THE BUILDING SHALL BE HIGH EFFICACY WITH A MANUAL ON/OFF SWITCH AND CONTROLLED BY MOTION SENSOR & PHOTO CONTROL. FIXTURE SHALL BE DOWNWARD LIGHTING. SWITCH 3-WAY SWITCH SWITCH WITH VACANCY SENSOR. SWITCH WITH DIMMER TYP. 110 RECEPTACLE RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. ARC-FAULT CIRCUIT INTERRUPTER PROTECTED RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. WATERPROOF RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. PROVIDE EXTERIOR GFCI WATERPROOF RECEPTACLES AT THE FRONT & REAR OF RESIDENCE WITHIN 6'- 6" OF GRADE. SURFACE MOUNT WALL SCONCE. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. COMBINATION SMOKE DETECTOR AND CARBON MONOXIDE DETECTOR UNIT. SEE NOTES THIS PAGE CEILING OR FLOOR MOUNTED HVAC REGISTER. O.L. SD/ CO CHANDELIER VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. SURFACE MOUNT CEILING LIGHT FIXTURE OR PENDANT. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. HIGH EFFICACY RECESSED LIGHT FIXTURE. SEE HIGH EFFICACY LIGHTING NOTES THIS PAGE. LIGHTS IN INSULATED CEILINGS SHALL BE IC RATED, HAVE ELECTRONIC BALLAST AND BE AIR- TIGHT (AT). UNDER-CABINET FLUORESCENT LIGHT. SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING. 3 D V QUADRUPLEX RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. 19 DN W01 D07 D09 D08 D11 D10 AFCI CO/SD CO/SD HE HE HEHE HE HEHE HE HE HE GFCI GFCI AFCI AFCI AFCI AFCI AFCIAFCI GFCI HE HE HE HE HE GFCI GFCI HE HE GFCI HE HE HE HE HE HE AFCI AFCI AFCI AFCI AFCI 1 A5.1 2 A5.1 3 A5.1 4 A5.1 1 A6.1 1 A6.1 2 A6.1 2 A6.1 F.C. 7'-10" F.C. 7'-10" DN SHOWER CURB BATH BALCONY BEDROOM CLOSET OFFICE CLOSET NOOK FIRST FLR. OUTLINE FIRST FLR. OUTLINE (E) BUILT-IN CABS ATTIC NO CHANGES NO CHANGES NO CHANGES NO CHANGES NO CHANGES NO CHANGES HALLWAY CLO. (N) FP WET BAR W.C. MASTER BATH MASTER CLOSET F.C. 7'-10" MASTER BDRM NO CHANGES NO CHANGES GAS SUPPLY & SHUTOFF DED. TO FPVV DOOR SCHEDULE - SECOND FLOOR NUMBER QTY FLOOR WIDTH HEIGHT TEMPERED DESCRIPTION D07 1 2 48 "80 " DOUBLE HINGED-DOOR P04 D08 1 2 30 "48 "HINGED-DOOR P04 D09 1 2 32 "80 "POCKET-DOOR P04 D10 1 2 30 "80 "HINGED-DOOR P04 D11 1 2 30 "80 " DOUBLE HINGED-DOOR P04 WINDOW SCHEDULE - SECOND FLOOR NUMBER QTY FLOOR WIDTH HEIGHT DESCRIPTION BOTTOM EGRESS TEMPERED W01 1 2 36 "36 " DOUBLE CASEMENT-LHL/ RHR 44"YES PROPOSED FLOOR PLANSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A4.2DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN 1 Scale: 1/4"=1'-0" PROPOSED SECOND FLOOR PLAN LEGEND: EXISTING CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION TO BE DEMOLISHED NEW INTERIOR CONSTRUCTION; 2x4 WD. STUD, 1/2" GYP. BD. EACH SIDE NEW EXTERIOR CONSTRUCTION NEW 1-HR FIRE RATED WALL; 2x4 WD. STUD, 5/8" TYPE "X" GYP. BD. EACH SIDE. SEE PLAN FOR LOCATIONS. SMOKE DETECTORS: A.SMOKE DETECTOR SYSTEM SHALL BE HARD WIRED, INTERCONNECTED TO SOUND SIMULTANEOUSLY AND EQUIPPED WITH BATTERY BACKUP. B.INSTALL DETECTORS IN EACH BEDROOM, AT EACH CORRIDOR/AREA NEXT TO THE BEDROOM, AT THE TOP OF STAIRS AND EACH STORY AND BASEMENT. C.MULTIPLE SMOKE DETECTORS ARE REQUIRED WHEN CEILING LEVELS/ ELEVATIONS CHANGE OR ARE INTERRUPTED BY ARCHITECTURAL ELEMENTS (CASED OPENINGS, ARCHWAYS, SKYLIGHT WELLS, ETC.) . D.SMOKE DETECTORS SHALL BE LISTED AND COMPLY WITH UL 217 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. CARBON MONOXIDE ALARMS: CARBON MONOXIDE ALARMS REQUIRED BY SECTION 420.6.2 SHALL BE INSTALLED AND MAINTAINED IN THE FOLLOWING LOCATIONS: A.OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOM (S). B.ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS. C.IN GROUP R-1 OCCUPANCIES; ON THE CEILING OF EVERY SLEEPING UNIT OR OTHER LOCATIONS WITHIN THE SLEEPING UNIT IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. D.CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH BATTERY BACK-UP. ALARM WIRING SHALL BE DIRECTLY CONNECTED TO THE PERMANENT BUILDING WIRING WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. E.WHERE MORE THAN ONE CARBON MONOXIDE ALARM IS REQUIRED TO BE INSTALLED WITHIN THE DWELLING UNIT OR WITHIN A SLEEPING UNIT, THE ALARM SHALL BE INTERCONNECTED IN A MANNER THAT ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. F.CARBON MONOXIDE ALARMS SHALL BE LISTED AND COMPLY WITH UL 2034 AND BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH NFPA 720 AND MANUFACTURERS INSTRUCTIONS. KITCHEN VENTILATION: WHERE COMBUSTION APPLIANCES OR SOLID-FUEL BURNING APPLIANCES ARE LOCATED INSIDE THE PRESSURE BOUNDARY, THE MAXIMUM ALLOWABLE NET EXHAUST FLOW OF THE TWO LARGEST EXHAUST FANS SHALL NOT EXCEED 15 CFM PER 100 SQ. FT. OF OCCUPIABLE SPACE, WHEN OPERATING AT FULL CAPACITY. IF THE DESIGNED TOTAL NET FLOW EXCEEDS THIS LIMIT, THE NET EXHAUST FLOW MUST BE REDUCED BY REDUCING THE EXHAUST FLOW OR PROVIDING COMPENSATING OUT-DOOR AIRFLOW (NOTE: IF MAKE-UP AIR FAN IS INSTALLED IT MUST BE ELECTRICALLY INTERLOCKED WITH THE LARGEST EXHAUST FAN) ATTIC/UNDERFLOOR INSTALLED FAU: A.UNIT SHALL BE ACCESSIBLE THROUGH AN OPENING AND PASSAGEWAY NOT LESS THAN THE LARGEST COMPONENT OF THE UNIT AND NOT LESS THAN 22"x30" B.THE DISTANCE FROM THE PASSAGEWAY ACCESS TO THE UNIT SHALL NOT EXCEED 20' C.THE WIDTH OF THE PASSAGEWAY SHALL BE UNOBSTRUCTED AND SHALL HAVE SOLID FLOORING NOT LESS THAN 24" WIDE FROM THE ENTRANCE OPENING TO THE UNIT. D.A LEVEL WORKING PLATFORM NOT LESS THAN 30" BY 30" SHALL BE PROVIDED IN FRONT OF THE SERVICE SIDE OF THE UNIT. E.A PERMANENT 120V RECEPTACLE OUTLET AND A LIGHTING FIXTURE SHALL BE INSTALLED NEAR THE UNIT. THE SWITCH CONTROLLING THE LIGHTING FIXTURE SHALL BE LOCATED AT THE ENTRANCE TO THE PASSAGEWAY. TYPICAL NOTES: LAUNDRY/BATHROOM VENTILATION: FOR LAUNDRY ROOMS AND BATHROOMS WITHOUT AN OPERABLE WINDOW: A.PROVIDE MECHANICAL VENTILATION SYSTEM CAPABLE OF 5 AIR CHANGES/HR. TO EXTERIOR. B.USE SMOOTH METAL DUCT FOR DRYER EXHAUST WITH A MAX. LENGTH OF 14', TO OUTSIDE WITH BACKDRAFT DAMPER AND TWO 90° ELBOWS AND A MIN. OF 4" DIA. C.TERMINATION OF ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MINIMUM OF 3 FEET FROM PROPERTY LINES OR ANY OPENINGS INTO THE BUILDING (i.e., DRYERS, BATH AND UTILITY FANS, ETC., MUST BE 3 FEET AWAY FROM DOORS WINDOWS, OPENING SKYLIGHTS OR ATTIC VENTS). D.EXHAUST FANS SHALL HAVE A MIN. OF 50 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR CONTINUOUS VENTILATION AND BE ENERGYSTAR COMPLIANT AND BE EQUIPPED WITH A HUMIDISTAT AND HUMIDITY CONTROL. AND BE SWITCHED SEPARATELY FROM LIGHTING SYSTEM. KITCHEN ELECTRICAL: A.ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER(AFCI). B.PROVIDE AFCI AND GFCI PROTECTION AT ALL RECEPTACLES SERVING KITCHEN COUNTERTOPS. C.AT EACH KITCHEN AND DINING AREA COUNTER SPACE WIDER THAN 12", LOCATE A RECEPTACLE SO THAT NO POINT ALONG THE COUNTER WALL IS OVER 24" FROM A RECEPTACLE. COUNTERTOP RECEPTACLES REQUIRED WITHIN 24" EACH SIDE OF A BREAK IN THE CONTINUOUS COUNTERTOP SURFACE (SINKS-STOVES). D.REQ'D RECEPTACLES MOUNTED ON THE SIDES OF CABINETS SHALL BE A MAXIMUM OF 12" BELOW THE COUNTERTOP SURFACE WITH A MAXIMUM OF 6" COUNTERTOP OVERHANG. E.PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS FOR COUNTER RECEPTACLES. BATHROOM ELECTRICAL: A.PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER RECEPTACLES, LIGHTS, FANS, ETC. (EXCEPTION-WHERE THE CIRCUIT SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED). B.ALL BRANCH CIRCUITS TO BE PROTECTED BY GROUND FAULT CIRCUIT INTERRUPTER (GFCI). LAUNDRY ELECTRICAL: A ALL BRANCH CIRCUITS TO BE PROTECTED BY ARC-FAULT (AFCI) CIRCUIT INTERRUPTER AND GROUND FAULT (GFCI) CIRCUIT INTERRUPTER. B PROVIDE 20AMP DEDICATED BRANCH CIRCUIT TO SUPPLY THE LAUNDRY RECEPTACLE OUTLET. C MINIMUM 30 AMP DEDICATED CIRCUIT FOR DRYER PER CEC 220.54. HIGH EFFICACY LIGHTING: A.ALL LIGHTING SHALL BE HIGH EFFICACY AS DEFINED BY CEC TABLE 150.0-A B.ALL PERMANENTLY INSTALLED SCREW-BASED LIGHT FIXTURES SHALL CONTAIN SCREW-BASED JA8 (JOINT APPENDIX 8) COMPLIANT LAMPS AND BE MARKED AS JA8-2019 OR JA8-2019-E. CEC 150.0(k)G C.ALL JA8 COMPLIANT LIGHT FIXTURES INSTALLED IN CEILING RECESSED DOWNLIGHTS, LED LUMINARIES WITH INTEGRAL SOURCES, PIN-BASED LED LAMPS, AND GU24 BASED LED LIGHT SOURCES SHALL BE CONTROLLED BY VACANCY SENSORS OR DIMMERS. D.AT LEAST ONE FIXTURE IN EACH BATHROOM, GARAGE, LAUNDRY ROOM, AND UTILITY ROOM SHALL BE CONTROLLED BY A VACANCY SENSOR. E.ALL LIGHTING SHALL BE SWITCHED SEPARATELY FROM EXHAUST FANS (EXCEPT FOR KITCHEN EXHAUST HOODS). F.ALL UNDER CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING SYSTEMS. G.GARAGE, LAUNDRY, AND UTILITY ROOMS: LIGHTING INSTALLED IN GARAGES, LAUNDRY, AND UTILITY ROOMS SHALL BE HIGH EFFICACY AND CONTROLLED BY VACANCY SENSORS. H.HIGH EFFICACY LIGHTING IS NOT REQUIRED IN CLOSETS OF LESS THAN 70 SF. I.OUTDOOR LIGHTING PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY AND CONTROLLED WITH A MANUAL ON/OFF SWITCH AND BY PHOTO CONTROL AND A MOTION SENSOR. PER ENERGY 110.9. J.ALL OTHER ROOMS: LIGHTING INSTALLED IN ALL OTHER ROOMS SHALL BE HIGH EFFICACY OR SHALL BE CONTROLLED BY EITHER DIMMERS OR VACANCY SENSORS. PLUMBING: A.ALL NEW TOILETS SHALL HAVE AN EFFECTIVE FLUSH VOLUME NOT TO EXCEED 1.28 GALLONS PER FLUSH. B.ALL NEW LAVATORY FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.2 GALLONS PER MINUTE AT 60 PSI. C.ALL NEW SHOWERHEADS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. D.MULTIPLE SHOWERHEADS SERVING ONE SHOWER - COMBINED FLOW RATE OF ALL SHOWERHEADS AND/OR OTHER SHOWER OUTLETS CONTROLLED BY A SINGLE VALVE SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 80 PSI. E.ALL NEW KITCHEN FAUCETS SHALL HAVE A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. KITCHEN FAUCETS MAY TEMPORARILY INCREASE THE FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER MINUTE AT 60 PSI AND MUST DEFAULT TO A MAXIMUM FLOW RATE OF 1.8 GALLONS PER MINUTE AT 60 PSI. BATHROOM: A.WATER CLOSETS SHALL BE LOCATED IN SPACES NOT LESS THAN 30" IN WIDTH AND 24" IN FRONT. B.WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT EXPOSURE TO WATER. CRC 702.3.7.1 C.BACKER FOR SHOWER AND TUB SHOWER WALLS TO BE FIBER-CEMENT, FIBER REINFORCED CEMENTITIOUS BACKER UNITS, GLASS MAT GYPSUM BACKERS OR FIBER-REINFORCED GYPSUM BACKERS TO A MIN HEIGHT OF 72" ABOVE THE FLOOR. D.USE 2X8 WOODEN BACKING IN ALL BATHROOM WALLS AT WATER CLOSET SHOWER AND BATHTUB, LOCATED AT 34" FROM FLOOR TO CENTER OF THE BACKING SUITABLE FOR THE ADDITION OF GRAB BARS. E.DOORS AND PANELS OF TUB AND SHOWER ENCLOSURES SHALL BE FULLY TEMPERED LAMINATED SAFETY GLASS OR APPROVED PLASTIC. F.SHOWER COMPARTMENTS SHALL HAVE MIN INTERIOR FLOOR AREA OF 1024 SQ IN AND ABLE TO CONTAIN A 30" DIA. CIRCLE. G.SHOWER AND TUB SHOWER COMBINATION IN ALL BUILDING SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. ELECTRICAL LEGEND (ALL LIGHTING TO BE HIGH EFFICACY) AFCI GFCI WP DOOR SCHEDULE NOTES: 1.DO NOT ORDER DIRECTLY OFF THIS SCHEDULE. FIELD VERIFY ROUGH OPENINGS PRIOR TO PLACING ORDER. WHEN ALL ROUGH OPENINGS ARE FRAMED, NOTIFY PROJECT MANAGER AND OWNER SO THAT A WALKTHROUGH CAN BE SCHEDULED TO REVIEW OPENINGS AND DOOR OPERATION PRIOR TO PLACING DOOR ORDER. 2.ALL PANELS OF GLAZING IN DOORS TO BE TEMPERED. 3.VERIFY DOOR MANUF. AND FINISH WITH OWNER PRIOR TO PLACING ORDER. WINDOW SCHEDULE NOTES: 1.DO NOT ORDER DIRECTLY OFF THIS SCHEDULE. WINDOW MEASUREMENTS SHOWN ARE APPROXIMATE, THE INTENTS IS TO USE THE MANUF. STANDARDS SIZES WHEREVER POSSIBLE. WHERE ALL ROUGH OPENINGS ARE FRAMED, NOTIFY PROJECT MANAGER AND OWNER SO THAT WALKTROUGH CAN BE SCHEDULED TO REVIEW OPENINGS AND WINDOW OPERATION PRIOR PLACING WINDOW ORDER. 2.VERIFY CODE COMPLIANCE OF NOTED EGRESS WINDOWS WITH MANUF. PRIOR TO PLACING ORDER. WINDOWS MARKED "EGRESS" TO HAVE BOTTOM OF CLEAR OPENING NO MORE THAN 44" A.F.F.; MINIMUM NET CLEAR OPENABLE DIMENSIONS - HEIGHT: 24"; WIDTH: 20"; AREA: 5.7 SF. 3.SEE TITLE 24 DOCUMENTS FOR MAXIMUM U-FACTORS AND SHGC VALUES. CONTRACTOR NOT TO WASH WINDOWS OR REMOVE LABELS PRIOR TO INSPECTION AND VERIFICATION OF VALUES. HE EXHAUST FAN/EXHAUST FAN/LIGHT COMBO. SEE BATH ELECTRICAL NOTES, THIS PAGE. 'W' INDICATES CONTINUOUSLY OPERATING MULTI-SPEED WHOLE BUILDING VENTILATION FAN. SEE WHOLE BUILDING VENTILATION NOTES THIS PAGE. OUTDOOR LIGHT. EXTERIOR LIGHTING ATTACHED TO THE BUILDING SHALL BE HIGH EFFICACY WITH A MANUAL ON/OFF SWITCH AND CONTROLLED BY MOTION SENSOR & PHOTO CONTROL. FIXTURE SHALL BE DOWNWARD LIGHTING. SWITCH 3-WAY SWITCH SWITCH WITH VACANCY SENSOR. SWITCH WITH DIMMER TYP. 110 RECEPTACLE RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. ARC-FAULT CIRCUIT INTERRUPTER PROTECTED RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. WATERPROOF RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER. PROVIDE EXTERIOR GFCI WATERPROOF RECEPTACLES AT THE FRONT & REAR OF RESIDENCE WITHIN 6'- 6" OF GRADE. SURFACE MOUNT WALL SCONCE. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. COMBINATION SMOKE DETECTOR AND CARBON MONOXIDE DETECTOR UNIT. SEE NOTES THIS PAGE CEILING OR FLOOR MOUNTED HVAC REGISTER. O.L. SD/ CO CHANDELIER VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. SURFACE MOUNT CEILING LIGHT FIXTURE OR PENDANT. VERIFY STYLE WITH HOMEOWNER PRIOR TO INSTALLATION. HIGH EFFICACY RECESSED LIGHT FIXTURE. SEE HIGH EFFICACY LIGHTING NOTES THIS PAGE. LIGHTS IN INSULATED CEILINGS SHALL BE IC RATED, HAVE ELECTRONIC BALLAST AND BE AIR- TIGHT (AT). UNDER-CABINET FLUORESCENT LIGHT. SHALL BE SWITCHED SEPARATELY FROM OTHER LIGHTING. 3 D V QUADRUPLEX RECEPTACLE. BRANCH CIRCUIT PROTECTED BY ARC-FAULT CIRCUIT INTERRUPTER. SEE ELECTRICAL NOTES THIS PAGE. 20 D01D01 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" (E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E) (E)(E)(E)(E)(E)(E)(E)(E) D01D01 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" (E) (E) (E)(E)(E)(E) (E)(E)(E) W01 W03 D02 W02 W03 D02 W02 W03W03 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" (E)(E)(E)(E) (E) (E) (E)(E)(E)(E) (E) W01 W03 D02 W02 W03 D02 W02 W03W03 D03D03 W01 D03 W01 D03 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" (E) (E) (E)(E) (E) (E)(E) (E) (E)(E)(E) D03D03 W01 D03 W01 D03 PROPOSED EXTERIORELEVATIONSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A5.1DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN 1 Scale: 1/4"=1'-0" PROPOSED FRONT ELEVATION 2 Scale: 1/4"=1'-0" PROPOSED RIGHT ELEVATION 3 Scale: 1/4"=1'-0" PROPOSED REAR ELEVATION 4 Scale: 1/4"=1'-0" PROPOSED LEFT ELEVATION 21 W03W03 D11 W03 W02 D06 D11 W03 W02 D06 D08D08 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" UTILITY DINING KITCHEN HALL FORAML DINING LIVING BEDROOM HALL MASTER BEDROOM 2 A6.1 W03W03 D11 W03 W02 D06 D11 W03 W02 D06 D08D08 D07 W01 D05 D07 W01 D05D05D05 1'-9"8'-9"1'-2"7'-10"4'-4 1/2"(E) GRADE 0'-0" (E) 1ST F.F. +1'-9" (E) 1ST F.C. +10'-6" (E) 2ND F.F. +11'-8" (E) 2ND F.C. +19'-6" (E) TOP RIDGE +23'-10 1/2" VESTIBULE FORMAL DINING GUEST BEDROOM CLO. OFFICE MASTER BEDROOM MASTER BATH 1 A6.1 D07 W01 D05 D07 W01 D05D05D05 BUILDING SECTIONSSHEET: SCALE: DRAWN BY:DRAWINGS PROVIDED BY:BUILDING PERMIT SET 12/7/2021 A6.1DESCRIPTIONDATE:PROJECT DESCRIPTION:TKACHEFF RESIDENCE20601 BROOKWOOD LANESARATOGA, CA 95070BYDATENO.SHEET TITLE:DeMattei Construction, Inc.1794 The Alameda, San Jose,CA. 95126P: (408) 295-7516F: (408) 286-6589LIC.# B-47845512/7/2021DISCLAIMER:THIS DOCUMENT CONTAINSCONFIDENTIAL AND PROPRIETARYINFORMATION THAT IS INTENDED FORTHE USE OF "De Mattei Construction Inc."DRAWINGS SHOULD NOT BEREPRODUCED OR DIVULGED, INWHOLE OR IN PART, WITHOUT WRITTENAUTHORIZATION FROM "De MatteiConstruction Inc." "De Mattei ConstructionInc." CANNOT BE HELD LIABLE IN THEEVENT THE DRAWINGS AREREPRODUCED OR DIVULGED WITHOUTWRITTEN AUTHORIZATION.AS SHOWN 1 Scale: 1/4"=1'-0" BUILDING SECTION 2 Scale: 1/4"=1'-0" BUILDING SECTION 22 Download full resolution images Available until Mar 4, 2022 From: To:Nicole Johnson; Kevin Meek; John Cherbone Subject:Orchard Update dormant season 22" Date:Wednesday, February 2, 2022 12:52:11 PM CAUTION: This email originated from outside your organization. Exercise caution when opening attachments or clicking links, especially from unknown senders. Hi all Not too much to report in the orchard over the winter. Though I did want to share that our remediation efforts for the oak root fungus disease are underway. Hope all is well and please let me know if I can answer any questions. Thanks Tasks in dormant season: - Dormant spray of organic materials to control various fungal pathogen and soft bodied insects. Complete. - Pruning of prune plums- to be completed in late winter (March) Oak Root Fungus remediation - Postponed the big plant out to next winter and have contracted with a grower to grow us trees on a resistant rootstock. All trees will be ready next Dec/Jan. -Installed splitters on the spray heads to keep root crowns dry - We are 95% complete with the root crown excavations. Over the years, soil has piled up on the trunks of the trees. Some trees were buried at least 12” deeper than originally planted. We have exposed the trunks and some, all the way to the root flare. This will help the trees survive longer in an oak root fungus soil. As mentioned before, it’s only a matter of time that the ORF kills these trees (if it is around the roots). Taking these steps will prolong the trees life. And now that this pathogen is identified, all new trees will be on resistant rootstocks to ensure longevity. Here is a short video of the air spading and a couple pictures of how the ORF girdles the tree trunk underground. The circled area is where the fungus has eaten away the cambium. Once the cambium is eaten away all around the tree, it is cut off from the water and nutrients that the roots absorb and the tree dies. By exposing the trunk and the root crown, we look to dry out the fungus so that it cannot spread. 23 Click to Download IMG_2033.MOV 91.2 MB 24 Matthew Sutton Founder/President Orchard Keepers Inc. 25 Historic Resource Inventory Year/Fiscal Year Notes Added Montpere Way 18500 2015 Shubert Dr 19277 2017-2018 Lutheria Way Entrance Posts 14200 & 14221 Lutheria Way 2018-2019 Saratoga Av 13601 (St Andrew's)2018-2019 DeHavilland Drive 19461 2019-2020 Entrance Planter DeHavilland Drive 19152 2019-2020 Entrance Planter DeHavviland Drive 19174 2021-2022 Eichler Home Park Place 20390 2019-2020 Saratoga Federated Church Bell Shubert Drive 19201 2019-2020 Entrance Planter Shubert Drive 19401 2019-2020 Entrance Planter Montpere Way 18485 2019-2020 Home Orchard Road 20331 2019-2020 Peck House Saratoga-Los Gatos Road 20450 2020-2021 Historical Park Saratoga-Los Gatos Road 20450 2020-2021 Interurban Stop Discontinued Allendale 19365 2017 Owner did not want house on Inventory Orchard Road 20328 2019 (Stransky)Letter sent for 45 day comment period. Period up on January 14th. On January 2, 2019, staff was informed that the Orchard Road 20350 2019 (Stransky)Letter sent for 45 day comment period. Period up on January 14th. Owner has contacted City and is hesitant about being Elva Ave - Russian Church 14220 2019 (Stransky)Letter sent for 45 day comment period. Period up on January 14th. Church responded that they do not want to be DeHavilland 19222 2021(Lopresto/Shastri)Let sent for 45 day comment period. Period ended 11/8/2021. No response from the owner. DeHavilland 19223 2021 (Lopresto/Shastri)Let sent for 45 day comment period. Period ended 11/8/2021. No response from the owner. Saratoga Ave 13650 (Library)2021 (Stransky)Hold Saratoga Ave 13718 (Sacred Heart)2021 (Lopresto)(Owner Requested to Hold Saratoga-Los Gatos Road 20318 2021 (Stransky)Owner Requested to Hold La Palmoa Ave 20295 2021 (Stransky)Owner Requested to Hold DeHavilland 19246 2022 (Lopresto/Shastri)Let sent for 45 day comment period. Period ended 01/17/22. No response from the owner. Landmarks Added Peach Hill Road 15320 2020-2021 Landmark and Mills Act Carey House Orchard Road 20331 2019-2020 Landmark and Mills Act Peck House Shubert Dr 19277 2020-2021 Landmark and Mills Act Kenji Matsuda House Discontinued Bella Vista 20021 2014 Lack of owner consent Big Basin Way 14501-14503 2014 Lack of owner consent plus not eligible as it lacks sufficient integrity to its original design Fruitvale 14251 2014 Lack of owner consent Big Basin Way 14519 2014 Lack of owner consent 1Big Basin Way (20640 Third St) 4413-14415 2014 Lack of owner consent plus not eligible as it lacks sufficient integrity to its original design Big Basin Way 14495 2014 Lack of owner consent plus not eligible as it lacks sufficient integrity to its original design Pierce Rd 14754 2014 Lack of owner consent Old Grandview Ranch 2015 Owner did not want house as a landmark Heritage Tree Inventory Added Palm Trees - Yerba Santa Court 2017-2018 Point of Interest Markers Installed Theater of the Glade Site Point of Interest Marker 2017-2018 Saratoga Ave/Saratoga-Los Gatos Road Blossom Festival Point of Interest Marker 2017-2018 Saratoga Ave/Saratoga-Los Gatos Road Ohlone Indians 2019/2020 Wildwood Park Saloons 2019/2020 within the road right of way adjacent to 14535 Big Basin Way Saratoga Paper Mill 2019/2020 within the road right of way adjacent to 14650 Big Basin Way Caledonia Pasteboard Mill 2019/2020 Wildwood Park Approved Big Basin Way near the Buy and Save Market McCartysville Big Basin Way where Bank of America is located-the parking lot is Immigrating to CA Quito Road El Quito Olive Farm Saratoga-Los Gatos Road Glen Una Ranch Big Basin Way and Third St Saratoga Vitaphone Other Village Design Guidelines 2019 City Council meeting scheduled Approved by CC 8/21/19 Memorial Arch 2019/2020 Completed February 2020 Completed Feb 2020 Heritage Orchard Master Plan Update 2020/2021 City Council Approved by CC 12/02/20 Publications Heritage Tree Guidebook 2017 FAQ's Historic Preservation 2017 FAQ's Heritage Trees 2017 FAQ's Mills Act 2017-2018 FAQ's Landmarks 2017-2018 Training Federal Fiscal Year Webinar CA Modern Architecture 2017/2018 Webinar Identifying and Treating Historic Wood 2018/2019 Webinar Examples in Sourcing and Repairing California's Historic 2018/2019 Deep Dive into the Secretory of Interior Standards 2019/2020 2/20/2020-Shah, Nugent & Johnson Eichler Home Tour 2019/2020 26 Project Status Worksheet APN/Location Address Staff/Commissioner Assigned Status 503 24 087 3rd Street 20640 TBD Owner working on obtaining documents 397 23 040 Lutheria Way 14321 Lopresto/Shastri 397 22 040 Orchard Road 20290 TBD 503 48 045 Congress Springs Rd 22000 (Quarry)Shah Loading Structure 503 23 008 Marion Rd 20602 Boyce-Bender 517 20 019 Montalvo Road 14900 TBD 389 26 021 Montpere Way 18530 Boyce-Bender 397 31 003 Saratoga Ave 14285 Lopresto 397 31 004 Saratoga Ave 14301 Lopresto 397 16 055 14120 Shadow Oaks - Tree 397 42 002 14250 Douglas Lane Memorial Park 517 12 036 14766 Oak St- Madronia Cemetery 397 30 053 13650 Saratoga Ave-Heritage Orchard TBD TBD TBD Harvest Day 2022 TBD May 2022 Ongoing Ongoing Johnson TBD Johnson HPC Recommendation to CC. CC meeting date TBD Staff Ongoing Ongoing Ongoing Potential Heritage Resource Inventory Candidates Other Historic Landmarks Point of Interest Markers (POI) Heritage Plaques/Signage Events Budget Other Blossom Festival 2022 State of the City 2022 Arbor Day 2022 Preservation Month 2022 Approved 11,600.00 11,600.00 Community Outreach via Social Media Training Balance Saratoga Ave Heritage Lane Inventory Village Inventory Heritage Lane Ord. Amendment Heritage Resource Inventory Ord. Amendment Grover House Development Update Page 2 of 2 2/1/2022 27